DeviceNet to SCANport Communication Module with Digital Inputs Parameters

B-17

DeviceNet to SCANport
Communication Module with
Digital Inputs Parameters

The following table provides information on the DeviceNet to
SCANport Communication Module with Digital Inputs parameter set.

Important:

When accessing this parameter set

through the

DeviceNet Parameter Class, add

the adapter’s parameter number

to

the number of the last parameter of the SCANport device.

When

accessing this parameter set

through the vendor-specific SCANport

Variables-Linear Class, add the adapter’s parameter number to
4000H.

#

Name

Valid Values/

Settings

Default

Writable

Reset or

Power

Cycle

Description

1

SCANport

Adapter

0-7

NA

No

No

Identifies the port number to which the adapter
is connected on the SCANport product.

2

DN Node

Address

0-63

63

Yes

Yes

Identifies the DeviceNet Node Address for the
adapter.

3

DN Data Rate

125K
250K
500K

Auto

Auto

Yes

Yes

Identifies the data rate used on the DeviceNet
network.
Important: At least one node on your
DeviceNet network must be configured to a
data rate (125, 250, or 500 K), not autobaud.

4

Cmd/Stat Con-

fig

Off, On

On

Yes

Yes

Determines whether to pass logic command and
analog reference control data from a DeviceNet
connection to a SCANport product.

5

Datalink A Cfg

Off, On

Off

Yes

Yes

Determines whether to pass control data
contained in datalink A from a DeviceNet
connection to the SCANport product.

6

Datalink B Cfg

Off, On

Off

Yes

Yes

Determines whether to pass control data
contained in datalink B from a DeviceNet
connection to the SCANport product.

7

Datalink C Cfg

Off, On

Off

Yes

Yes

Determines whether to pass control data
contained in datalink C from a DeviceNet
connection to the SCANport product.

8

Datalink D Cfg

Off, On

Off

Yes

Yes

Determines whether to pass control data
contained in datalink D from a DeviceNet
connection to the SCANport product.

Important:

For information on accessing and editing parameters, refer to Chapter 3, Configuring the DeviceNet to SCANport

Communication Module with Digital Inputs.