DeviceNet to SCANport Communication Module with Digital Inputs Parameters

5. In the Tx field, enter 4 for the size of the I/O output.

6. In the Send Rate field, enter the desired time for the interval

between messages.

7. Click OK.

Important: After you have configured the scanner and adapter for
Cyclic, you can verify the desired send rate is used by viewing the
COS/CYC Interval (28) parameter in the adapter.

Polled and COS Allocation

You can enable both polling and COS allocations. This lets the
scanner poll the adapter at a fixed interval and the adapter report its
status changes to the scanner after they occur.

Enabling Polling and COS in the Adapter

Refer to both the “Polled Allocation” and the “COS (Change of State)
Allocation” sections in this chapter for information.

Enabling Polling and COS in the Scanner

Use RSNetWorx to enable polling in the scanner. Refer to Chapter 4,
Configuring a Scanner to Communicate with the Adapter, for more
information on configuring the scanner.

Polling and COS must be enabled in the Edit Device I/O Parameters
dialog box.

Figure B.6
Edit Device I/O Parameters Dialog Box for Polling and COS

1. In the Polled section, click on the box next to Polled. A “✔”

appears.

2. In the Rx field, enter the size for the I/O input. Enter 4 for each

datalink enabled and 6 if Com/Ref is enabled. For example, if
Cmd/Ref and all 4 datalinks are enabled, you would enter 22.