Configuring a Scanner to Communicate with the Adapter

8. Make the changes as necessary. You must configure your PLC

based on how your adapter’s parameters are configured and how
you want your module to send and receive data from the network.
Refer to the following table:

9. Click OK to return to the Scanlist screen.

10. Click on the Apply button. A dialog box appears asking if you

wish to download the changes to the device. Click on Yes.

Important: If the processor is not in Program mode, a dialog box
will appear stating which mode the processor is in. Clicking on the
OK button returns the Scanlist screen without downloading any
information to the processor. You must now place the processor in
program mode and repeat the apply function.

11. Click on the Input tab to view the input table map. From this

screen you can customize the arrangement of the scanner’s data
table. Refer to the RSNetWorx online help for additional
information.

Figure 4.27
Input Data Table Map Screen

If Using:

Refer To:

Polled

Polled Allocation on page B-5.

COS (Change of State)

COS (Change of State) Allocation on page B-7.

Cyclic

Cyclic Allocation on page B-8.

Polled and COS

Polled and COS Allocation on page B-10.

Polled and Cyclic

Polled and Cyclic Allocation on page B-11.