beautypg.com

Rockwell Automation 2100-GK61 DeviceNet to SCANport User Manual

Page 33

background image

Publication 2100-UM001B-EN-P – January 2001

Configuring the DeviceNet to SCANport Communication Module with Digital Inputs

3-3

Using RSNetWorx to Edit Your
Adapter’s Parameters

The following instructions describe how to use RSNetWorx for
DeviceNet in online mode to edit your adapter’s parameters.

1. Use RSLinx to configure the DeviceNet drivers for your system

using the Configure Drivers option in the Communications
menu.

2. Start RSNetWorx for DeviceNet. The RSNetWorx for DeviceNet

screen appears as seen in Figure 3.1.

Figure 3.1
RSNetWorx for DeviceNet Screen

3. In the Network menu, select Online, or click on the Online icon

as indicated in Figure 3.2.

4. The Browse Network screen appears asking to select which

network you wish to go online with. Select the DeviceNet
network desired and click on OK.