Class code 0x0f — parameter object, Class attributes instances – Rockwell Automation 2100-GK61 DeviceNet to SCANport User Manual
Page 164
![background image](/manuals/580743/164/background.png)
Publication 2100-UM001B-EN-P – January 2001
C-10
DeviceNet Objects
Class Code 0x0F — Parameter
Object
The Parameter Object provides a known, public interface for device
configuration data. This object also provides all the information
necessary to define and describe each individual configuration
parameter of a device.
Class Attributes
Instances
The number of instances varies based on the number of parameters in
your SCANport product. The adapter parameters immediately follow
the SCANport product parameters.
Attribute
ID
Access
Rule
Name
Data
Type
Description
1
Get
Revision
UINT
Revision of this object.
First revision, value = 1.
2
Get
Max Instance
UINT
Maximum instance
number of an object
currently created in this
class level of the device.
8
Get
Parameter
Class
Descriptor
WORD
Bits that describe
parameters.
9
Get
Configuration
Assembly
Instance
UINT
Instance number of the
configuration assembly.
This attribute is set to zero
because a configuration
assembly is not
supported.
10
Set
Native
Language
USINT
Language ID for all
character array accesses.
0 = English
1 = French
2 = Spanish
3 = Italian
4 = German
5 = Japanese
6 = Portuguese
Instance
Description
1 through n - 41
➀
SCANport Product Parameters
n - 41 through n
➀
Module Parameters
➀
The value of n is the maximum instance in the object. This value is obtainable via class
attribute 2.