Rockwell Automation 2100-GK61 DeviceNet to SCANport User Manual
Page 144
Publication 2100-UM001B-EN-P – January 2001
B-18
DeviceNet to SCANport Communication Module with Digital Inputs Parameters
9
Idle Flt Action
Fault
Zero Data
Hold Last
Fault Cfg
Fault
Yes
No
Determines the action the adapter should
instruct the SCANport product to take if the
adapter detects that the PLC is set to program
mode.
Important: If you change this parameter’s
value, the user application may not be able to
control the product after a fault.
10
Comm Flt
Action
Fault
Zero Data
Hold Last
Fault Cfg
Fault
Yes
No
Determines the action the adapter should
instruct the SCANport product to take if the
adapter detects a network failure.
Important: If you change this parameter’s
value, the user application may not be able to
control the product after a fault.
#
Name
Valid Values/
Settings
Default
Writable
Reset or
Power
Cycle
Description
Important:
For information on accessing and editing parameters, refer to Chapter 3, Configuring the DeviceNet to SCANport
Communication Module with Digital Inputs.
!
ATTENTION:
Risk of severe
bodily injury or equipment
damage exists. The Idle Flt
Action (9) and Comm Flt
Action (10) parameters
allow the user to change the
default configuration that
would allow the module
and associated drive to
continue to operate if
communication is lost.
Precautions should be
taken to assure that your
settings for these
parameters and your
application do not create a
hazard of bodily injury or
equipment damage.
!
ATTENTION:Risk of severe
bodily injury or equipment
damage exists. The Comm Flt
Action (10) parameter allows the
user to change the default
configuration that would allow
the module and associated drive
to continue to operate if
communication is lost.
Precautions should be taken to
assure that your settings for
these parameters and your
application do not create a
hazard of bodily injury or
equipment damage.