Rockwell Automation 2100-GK61 DeviceNet to SCANport User Manual
Page 145
Publication 2100-UM001B-EN-P – January 2001
DeviceNet to SCANport Communication Module with Digital Inputs Parameters
B-19
11
Fault Cfg Logic
0 – 65535
0
Yes
No
Provides the logic command data to the
SCANport product when the adapter is
instructed to use the values for the Fault Cfg
parameters.
12
Fault Cfg Ref
0 – 65535
0
Yes
No
Provides the analog reference data to the
SCANport product when the adapter is
instructed to use the values for the Fault Cfg
parameters.
13
Fault Cfg A1 In
0 – 65535
0
Yes
No
Provides the first word of datalink A data to the
SCANport product when the adapter is
instructed to use the values for the Fault Cfg
parameters.
14
Fault Cfg A2 In
0 – 65535
0
Yes
No
Provides the second word of datalink A data to
the SCANport product when the adapter is
instructed to use the values for the Fault Cfg
parameters.
15
Fault Cfg B1 In
0 – 65535
0
Yes
No
Provides the first word of datalink B data to the
SCANport product when the adapter is
instructed to use the values for the Fault Cfg
parameters.
16
Fault Cfg B2 In
0 – 65535
0
Yes
No
Provides the second word of datalink B data to
the SCANport product when the adapter is
instructed to use the values for the Fault Cfg
parameters.
17
Fault Cfg C1 In
0 – 65535
0
Yes
No
Provides the first word of datalink C data to the
SCANport product when the adapter is
instructed to use the values for the Fault Cfg
parameters.
18
Fault Cfg C2 In
0 – 65535
0
No
No
Provides the second word of datalink C data to
the SCANport product when the adapter is
instructed to use the values for the Fault Cfg
parameters.
19
Fault Cfg D1 In
0 – 65535
0
Yes
No
Provides the first word of datalink D data to the
SCANport product when the adapter is
instructed to use the values for the Fault Cfg
parameters.
20
Fault Cfg D2 In
0 – 65535
0
Yes
No
Provides the second word of datalink D data to
the SCANport product when the adapter is
instructed to use the values for the Fault Cfg
parameters.
21
Digital Input
xxxx 0000 -
xxxx 1111
NA
No
No
Digital Input Status.
1 = power applied to Input
0 = no power at Input
#
Name
Valid Values/
Settings
Default
Writable
Reset or
Power
Cycle
Description
Important:
For information on accessing and editing parameters, refer to Chapter 3, Configuring the DeviceNet to SCANport
Communication Module with Digital Inputs.