Yokogawa Removable Chassis DX1000N User Manual
Page 68
1-60
IM 04L41B01-17E
Loading to External Input Channels (DX2000 Only)
The DX inputs the data loaded from the server to the external input channel as a 16-bit
signed integer type.
• Example 1
Load the values of the 16-bit unsigned integers assigned to register 30001 of
instrument C to external input channel 201.
30001
201
16-bit unsigned integer
External input channel
Register of instrument C
Command setting
R
201 - 201
3
30001
UINT16
• Example 2
Load the values of the 32-bit unsigned integers assigned to registers 32001 and
32002 of instrument C to external input channel 202. Only the smallest register
number need be specified in commands.
32-bit unsigned integer
32001
32002
202
External input channel
Register of instrument C
higher bytes
lower bytes
Command setting
R
202 - 202
3
32001
UINT32 _ B
Writing Measured Values to the Server
• Example
Write the measured value (16-bit signed integer) from channel 1 to register 40001 of
instrument A.
16-bit signed integer
Measurement channel
Register of instrument A
001
40001
Command setting
W
001 - 001
1
40001
INT16
Writing Computed Values to the Server
• Example
Write the computed values (32-bit signed integers) from channel 101 to registers
40001 and 40002 of instrument A, in the order lower 16 bits/higher 16 bits. Only the
smallest register number need be specified in commands.
32-bit signed integer
Computation channel
Register of instrument A
40001
40002
101
lower bytes
higher bytes
Command setting
W-R
101 - 101
1
40001
INT32_L
1.10 Using the Modbus Client Function