App index, Examples of setting commands, Checking the modbus operating status – Yokogawa Removable Chassis DX1000N User Manual

Page 107

background image

2-13

IM 04L41B01-17E

Using the Serial Interface

1

2

3

4

5

6

App

Index

E-M: Read to the communication input data (32-bit floating point type) from the

server/write the custom display value to the server (release numbers 4 and
later).

R can be selected on DX2000s with the external input channel (/MC1) installed.

R-M, W-M, and E-M can be selected on models with the computation function

(/M1 or /PM1) option installed.

• First/Last (DX’s channel numbers)

Enter the first and last channel numbers of input/output. The range of channels that

you can enter varies depending on the command type as follows:
R: 201 to 440, R-M: C01 to C60, W: 1 to 48, W-M: 101 to 160, E-M: C01 to C60

• Address

Enter the address of the slave device in the range of 1 to 247.

• Regi.

Set the register number of the slave.
For an input register, select in the range of 30001 to 39999 and 300001 to 365536.

For a hold register, select in the range of 40001 to 49999 and 400001 to 465536.

The register numbers you can specify vary depending on the command type. See

section 6.3.

• Type

Select INT16, UINT16, INT32_B, INT32_L, UINT32_B, UINT_L, FLOAT_B, or

FLOAT_L.

The register numbers you can specify vary depending on the command type. See

section 6.3.

Examples of Setting Commands

See page 1-36.

Checking the Modbus Operating Status

Displaying the Modbus Operating Status

◊ Press

DISP/ENTER and select INFORMATION > MODBUS MASTER.

Note

To display the

MODBUS MASTER on the screen selection menu, you need to change the

setting using the menu cutomize function. Operate as follows:
◊ Press

MENU

(to switch to setting mode), and select the

Menu

tab >

Menu customize

>

Display menu.

1. Select

INFORMATION > MODBUS MASTER

.

2. Press the

View soft key.

Address for a slave device

Register number

DX channels

Detail code

Status lamp

Cursor to select a command

(Used when resuming command transmission

to a slave device using the front panel keys)

Communication condition

2.6 Using the Modbus Master Function