3-46
IM 04L41B01-17E
p2 Where to write messages that you enter
using keys
COMMON All display groups
SEPARATE Display group that you specify
p3 Power failure message (OFF, ON)
p4 Message change (OFF, ON)
Input settings
Syntax
WU p1,p2
p1 Setting type (INPUT)
p2 How to detect values that exceed the scale
FREE
When the measurement range is
exceeded
OVER
When ±105% of the scale is
exceeded
Alarm settings
Syntax
WU p1,p2,p3,p4,p5
p1 Setting type (ALARM)
p2 Alarm suppression function (OFF, ON)
p3 Annunciator mode (OFF, ON)
p4 Sequence (ISA-A-4, ISA-A, ISA-M)
ISA-A-4 No lock-in
ISA-A Lock-in
ISA-M Double lock-in
p5 Color when no alarms are activated
(GREEN, WHITE)
Description Parameters p4 and p5 are valid when p3 is set to
ON.
Security settings
Syntax
WU p1,p2,p3,p4,p5
p1 Setting type (SECURITY)
p2 Key
OFF
Disables security features
KEYLOCK Locks the keys
LOGIN Enables the login function
p3 Communication
OFF
Disables security features
LOGIN Enables the login function
p4 Multi login (ON, OFF)
p5 Password management (ON, OFF)
Description • p4 and p5 are only valid on models with the
/AS1 advanced security option.
• On models with the /AS1 advanced security
option, p2 is fixed at LOGIN.
Media settings
Syntax
WU p1,p2,p3
p1 Setting type (MEDIA)
p2 Automatic saving (OFF, ON)
p3 Media FIFO (OFF, ON)
Example Use media FIFO.
WUMEDIA,ON,ON
Description Parameter p3 is valid when p2 is set to ON.
Computation settings
Syntax
WU p1,p2,p3,p4
p1 Setting type (MATH)
p2 Display on error
+OVER Positive overflow
-OVER Negative overflow
p3 Data when the SUM or AVE value overflows
ERROR Sets the computed result to
computation error
SKIP
Discards the data that overflowed
and continues the computation
LIMIT Process the data as follows:
• For measurement channels
that do not have linear scaling
specified, the DX sets the data
to the upper or lower limit of the
measurement range.
• For measurement channels that
have linear scaling specified,
the DX sets the data to the
specified scan upper or lower
limit.
• For computation channels,
the DX sets the data to the
specified span upper or lower
limit.
p4 Data when the MAX, MIN, or P-P value
overflows
OVER
Computes using the overflow data
SKIP
Discards the data that overflowed
and continues the computation
Report settings
Syntax
WU p1,p2,p3,p4,p5,p6,p7
p1 Setting type (REPORT)
p2 Report computation type 1
MAX
Maximum value
MIN
Minimum value
AVE
Average value
SUM
Integrated value
INST
Instantaneous value
p3 Report computation type 2
OFF
Disables report computation
MAX
Maximum value
MIN
Minimum value
AVE
Average value
SUM
Integrated value
INST
Instantaneous value
p4 Report computation type 3
Same as p3.
p5 Report computation type 4
Same as p3.
p6 Creation of “hourly+daily,” “daily+weekly,”,
and “daily+monthly” files
COMBINE Saves reports to one file.
SEPARATE Saves reports to separate files.
SEPARATE2 Saves reports to separate files
(DX100/DX200 format).
p7 Report template function (USE, NOT)
Description • For parameters p2 to p5, you cannot specify
the same computation type except OFF.
3.6 Basic Setting Commands