beautypg.com

Yokogawa Removable Chassis DX1000N User Manual

Page 163

background image

3-46

IM 04L41B01-17E

p2 Where to write messages that you enter

using keys
COMMON All display groups
SEPARATE Display group that you specify

p3 Power failure message (OFF, ON)
p4 Message change (OFF, ON)

Input settings

Syntax

WU p1,p2
p1 Setting type (INPUT)
p2 How to detect values that exceed the scale

FREE

When the measurement range is
exceeded

OVER

When ±105% of the scale is
exceeded

Alarm settings

Syntax

WU p1,p2,p3,p4,p5
p1 Setting type (ALARM)
p2 Alarm suppression function (OFF, ON)
p3 Annunciator mode (OFF, ON)
p4 Sequence (ISA-A-4, ISA-A, ISA-M)

ISA-A-4 No lock-in
ISA-A Lock-in
ISA-M Double lock-in

p5 Color when no alarms are activated

(GREEN, WHITE)

Description Parameters p4 and p5 are valid when p3 is set to

ON.

Security settings

Syntax

WU p1,p2,p3,p4,p5
p1 Setting type (SECURITY)
p2 Key

OFF

Disables security features

KEYLOCK Locks the keys
LOGIN Enables the login function

p3 Communication

OFF

Disables security features

LOGIN Enables the login function

p4 Multi login (ON, OFF)
p5 Password management (ON, OFF)

Description • p4 and p5 are only valid on models with the

/AS1 advanced security option.

• On models with the /AS1 advanced security

option, p2 is fixed at LOGIN.

Media settings

Syntax

WU p1,p2,p3
p1 Setting type (MEDIA)
p2 Automatic saving (OFF, ON)
p3 Media FIFO (OFF, ON)

Example Use media FIFO.

WUMEDIA,ON,ON

Description Parameter p3 is valid when p2 is set to ON.

Computation settings

Syntax

WU p1,p2,p3,p4
p1 Setting type (MATH)

p2 Display on error

+OVER Positive overflow
-OVER Negative overflow

p3 Data when the SUM or AVE value overflows

ERROR Sets the computed result to

computation error

SKIP

Discards the data that overflowed
and continues the computation

LIMIT Process the data as follows:

• For measurement channels

that do not have linear scaling
specified, the DX sets the data
to the upper or lower limit of the
measurement range.

• For measurement channels that

have linear scaling specified,
the DX sets the data to the
specified scan upper or lower
limit.

• For computation channels,

the DX sets the data to the
specified span upper or lower
limit.

p4 Data when the MAX, MIN, or P-P value

overflows
OVER

Computes using the overflow data

SKIP

Discards the data that overflowed
and continues the computation

Report settings

Syntax

WU p1,p2,p3,p4,p5,p6,p7
p1 Setting type (REPORT)
p2 Report computation type 1

MAX

Maximum value

MIN

Minimum value

AVE

Average value

SUM

Integrated value

INST

Instantaneous value

p3 Report computation type 2

OFF

Disables report computation

MAX

Maximum value

MIN

Minimum value

AVE

Average value

SUM

Integrated value

INST

Instantaneous value

p4 Report computation type 3

Same as p3.

p5 Report computation type 4

Same as p3.

p6 Creation of “hourly+daily,” “daily+weekly,”,

and “daily+monthly” files
COMBINE Saves reports to one file.
SEPARATE Saves reports to separate files.
SEPARATE2 Saves reports to separate files

(DX100/DX200 format).

p7 Report template function (USE, NOT)

Description • For parameters p2 to p5, you cannot specify

the same computation type except OFF.