Example Set the trend interval to the secondary trend

interval.
CV1

MS

Writes a message (display and

write)

Syntax

MS p1,p2,p3,p4
p1 Message number (1 to 100)
p2 Message write destination

GROUP A specified display group
ALL

All display groups

All display groups in the specified
batch group number (p4) when
multi batch /BT2 is in use

p3 Display group number

The display group number when p2 is set to
GROUP

Carries no meaning when p2 is set to ALL

p4 Message write destination batch group

number

Example Write the message in message number 8 to

display group 1.
MS8,GROUP,1

Description • If you omit p2, the message is written to all

display groups.

• Parameter p4 is only valid when multi batch

/BT2 is in use. When multi batch /BT2 is in
use, you cannot omit p4.

• Set parameters p3 and p4 by referring to the

table in section 3.3.

BJ

Write a free message

Syntax

BJ p1,p2,p3,p4,p5
p1 Message number (1 to 10)
p2 Message (up to 32 characters)
p3 Message write destination

GROUP A specified display group
ALL

All display groups

All display groups in the specified
batch group number (p5) when
multi batch /BT2 is in use

p4 Display group number

The display group number when p2 is set to
GROUP

Carries no meaning when p2 is set to ALL

p5 Message write destination batch group

number

Example Using message number 3, write the string

“ALARM” to all groups.
BJ3,ALARM,ALL

Description • If you omit p3, the message is written to all

display groups.

• Parameter p5 is only valid when multi batch

/BT2 is in use. When multi batch /BT2 is in
use, you cannot omit p5.

• Set parameters p3, p4, and p5 by referring to

the table in section 3.3.

EJ

Changes the login password

Syntax

EJ p1,p2,p3
p1 Old password (see the description)
p2 New password (see the description)
p3 New password (see the description)

Example Change the password from “PASS001” to

“WORD005.”
EJPASS001,WORD005,WORD005

Description • The password character lengths are indicated

below.
Release numbers 3 and earlier:

Up to 8 characters

Release numbers 4 and later:

Up to 20 characters

On models with the /AS1 advanced security

option:

Between 6 and 20 characters

• When you use password management (the

WU command) on models with the /AS1
advanced security option, this command is
invalid.

TL

Starts, stops, resets

computation (MATH) or clears

the computation dropout status

display

Syntax

TL p1,p2
p1 Type of operation

0

Start computation

1

Stop computation

2

Reset computation

3

Clear the computation data
dropout display

p2 Batch group number

0

All computation channels

1, 2, ... Batch group number

Example Start computation.

TL0

Description • You cannot use this command while the DX is

saving or loading setup data.

• You can use this command on models with the

/M1 or /PM1 option.

• When multi batch /BT2 is in use, p2 is valid

when p1 is set to 2 (reset computation). If you
omit p2, it is the same as setting p2 to zero. If
p2 is set to zero, the DX resets the values of
all computation channels.

• Set parameter p2 by referring to the table in

section 3.3.

DS

Switches the execution mode

between operation and setting

Syntax

DS p1

3.5 Control Commands