App index, Ps starts or stops recording, Ak clears alarm output (acknowledge alarms) – Yokogawa Removable Chassis DX1000N User Manual

Page 156: Cl executes manual sntp

background image

3-39

Commands

IM 04L41B01-17E

1

2

3

4

5

6

App

Index

p10 Tag prioritized display (ON, OFF)

Example Enable automatic display switching, switch to the

group display, turn on the scale display, and turn
off the digital display.
UD4,ON,GROUP,ON,OFF

Description • Parameter p2 is valid for the trend, digital, and

bar graph displays. Use the SE command to
set the switching interval.

• Parameters p3 to p7 are valid for the trend

display.

• When multi batch /BT2 is in use, you cannot

use this command in batch overview mode.

To switch the operation screen mode

Syntax

UD p1,p2,p3
p1 Display type (5)
p2 Operation screen mode (COMMON,

BATCH)
COMMON Batch overview mode
BATCH Batch single mode

p3 Batch group number

Description • You can use this command when multi batch

/BT2 is in use.

• Parameter p3 is valid when p2 is set to

BATCH.

• Set parameter p3 by referring to the table in

section 3.3.

PS

Starts or stops recording

Syntax

PS p1,p2
p1 Recording start or stop

0

Start

1

Stop

p2 Batch group number

0

All groups

1, 2, ... Batch group number

Example Start recording.

PS0

Description • When you start recording, the DX records

display, event, and report data to the internal
memory.

• Parameter p2 is valid when multi batch /BT2 is

in use. If you omit p2, it is the same as setting
p2 to zero.

• When the /AS1 advanced security option is

in use and the DX is in setting mode, it will
not start recording even if you send a PS0
command.

• Set parameter p2 by referring to the table in

section 3.3.

AK

Clears alarm output

(acknowledge alarms)

Syntax

AK p1,p2,p3
p1 Executes alarm acknowledge (0)

0

Alarm acknowledge

1

Individual alarm acknowledgment

2

Resets alarm display

p2 Channel number
p3 Alarm level (1 to 4)

Example Clear alarm output (acknowledge alarms).

AK0

Description • If you set p1 to 2 when annunciator mode is

on and the sequence is not ISA-M, an error
occurs.

• If you send this command with p1 set to 2

before acknowledging the alarms, nothing
happens.

• Set p2 by referring to the table in section 3.3.

• p2 and p3 are only valid when p1=1. The

setting p1=1 is only valid on models with the
/AS1 advanced security option.

EV

Executes manual sample,

generates a manual trigger, takes

a snapshot, or causes a timeout

Syntax

EV p1,p2
p1 Type of operation

0

Executes manual sampling.

1

Generates a manual trigger.

2

Takes a snapshot.

3

Causes a timeout in display data.

4

Causes a timeout in event data.

p2 Batch group number

0

All groups

1, 2, ... Batch group number

Example Execute manual sampling.

EV0

Description • EV1 is only valid when the key trigger is set to

ON using the event data sampling condition
command (TE command). This command is
equivalent to a key trigger.

• When multi batch /BT2 is in use, p2 is valid

when p1 is set to 3 or 4. If you omit p2, it is the
same as setting p2 to zero.

• Set parameter p2 by referring to the table in

section 3.3.

CL

Executes manual SNTP

Syntax

CL p1
p1 Executes manual SNTP(0)

Example Synchronize the clock.

CL0

CV

Switches between normal and

secondary trend interval

Syntax

CV p1
p1 Trend interval (0, 1)

0

Switches to the normal trend
interval

1

Switches to the secondary trend
interval

3.5 Control Commands