Modbus Server Function

Modbus Server Specifications

Communicate via ModbusTCP
Communication media: Ethernet 10Base-T
Port:

502/tcp (default value)

Command wait timeout: 1 minute. However, the timeout to receive the command after

starting to receive the command is 10 seconds.

Maximum number of connections:

2

Supported functions:

The functions that the DX supports are listed below.

Function

Code

Function

Operation

3

Read the hold register (4XXXXX) The client device reads the communication input data.

4

Read the input register

(3XXXXX)

The client device reads the computed, measured,

alarm, and time data of the DX.

6

Single write to hold register

(4XXXXX)

The client device writes to the communication input

data or external input channel of the DX.

8

Loopback test

The client device performs a loopback test of the DX.

16

Write to the hold register

(4XXXXX)

The master device writes to the communication input

data or external input channel of the DX.

Register assignments (shared with the Modbus slave function)

Measurement ch.

Computation ch.

External input ch.

Measurement ch.

Computation ch.

External input ch.

Time

Measured data

Alarm status

Computed data

Alarm status

Measured data

Alarm status

Alarm list

Alarm list

Alarm list

Data type

16-bit signed integer

Bit string

32-bit signed integer

Bit string

16-bit signed integer

Bit string

Bit string

Bit string

Bit string

16-bit signed integer

Number

300001 to 300048

301001 to 301048

302001 to 302120

303001 to 303060

304001 to 304240

305001 to 305240

306001 to 306012

306021 to 306035

306041 to 306100

309001 to 309008

Data

Input register

Communication input data

Measured data on external input ch.

Data type

16-bit signed integer

32-bit floating point

16-bit signed integer

Number

400001 to 400060

400301 to 400420

401001 to 401240

Data

Hold register

Client

Read

Client

Read

Write

On Models with the PROFIBUS-DP Interface (/CP1 option)
On models with the PROFIBUS-DP interface (/CP1 option), the communication input
data for C01 to C24 (on the DX1000) or for C01 to C32 (on the DX2000) is reserved for
PROFIBUS-DP. The client device cannot write values to this communication input data.

6.3 Modbus Protocol Specifications