3-48

IM 04L41B01-17E

DX, the DX switches to the signature window
at memory stop, and there is no FTP transfer at
signing.
BIBATCH,SIGNIN1+2,ON,OFF

Description p3 and p4 are valid when p2 is set to SIGNIN1,

SIGNIN1+2, or SIGNIN1+2+3.

WO

Sets alarm and DO settings

Alarm and DO settings

Syntax

WO p1,p2,p3,p4,p5
p1 Alarm setting (ALARM)
p2 Reflash operation (ON, OFF, ON-1S, ON-

2S,)

p3 Interval for the low limit on the rate-of-

change (1 to 32)

p4 Interval for the high limit on the rate-of-

change (1 to 32)

p5 Hold/Not hold the alarm status display

HOLD
NONHOLD

Description • If annunciator is set to ON in the alarm

environment settings (using WU ALARM), p2
and p5 are fixed to the following values based
on the annunciator sequence.

Sequence

p2

p5

ISA-A-4

OFF

NONHOLD

ISA-A

OFF

HOLD

ISA-M

OFF

HOLD

• The meanings of the different p2 options are

indicated below.

p2

Duration for which the Reflash Relays Are

Deactivated

ON

500 ms

ON-1S

1 s

ON-2S

2 s

Internal switch settings

Syntax

WO p1,p2
p1 DO type (SWITCH)
p2 AND switch number

NONE

No AND setting

S01

Only specify S01

S01-Sxx Specify S01 to Sxx

where xx = {02 to 30}

Output relay settings

Syntax

WO p1,p2,p3,p4,p5
p1 DO type (RLY)
p2 Relay number

NONE

No AND setting

I01

Only specify I01

I01-Ixx Specify I01 to Ixx

where xx = {02 to 36}

p3 Energize/De-energize the relay

DE_ENERGIZE
ENERGIZE

p4 Hold/Not hold the relay

NONHOLD
HOLD

p5 Relay Action on ACK

NORMAL
RESET

Description Set parameter p2 by referring to the table in

section 3.3.

If annunciator is set to ON in the alarm
environment settings (using WU ALARM), p4 and
p5 are fixed to the following values based on the
annunciator sequence.

Sequence

p4

p5

ISA-A-4

NONHOLD

RESET

ISA-A

HOLD

RESET

ISA-M

HOLD

RESET

Query

WO[p1]?

Example Specify no AND operation of the output relays,

set the relay action to energize, and release the
relay output when the alarm ACK operation is
performed regardless of the alarm status.
WORLY,NONE,ENERGINE,HOLD,RESET

WH

Sets alarm hysteresis

Measurement channels

Syntax

WH p1,p2,p3
p1 Channel type (MEASURE)
p2 Hysteresis on high and low limit alarms (0 to

50)

p3 Hysteresis on difference high and low limit

alarms (0 to 50)

Computation channels

Syntax

WH p1,p2
p1 Channel type (MATH)
p2 Hysteresis on high and low limit alarms (0 to

50)

External input channels

Syntax

WH p1,p2
p1 Channel type (EXTERNAL)
p2 Hysteresis on high and low limit alarms (0 to

50)

Query

WH[p1]?

Example Set the high and low limit alarm hysteresis

for measurement channels to 4.0%, and the
difference high and low limit alarm hysteresis to
0.0%.
WHMEASURE,40,0

Description You can specify computation channels on

models with the /M1 or /PM1 math option. You
can specify external input channels on models
with the external input channel option.

XV

Sets the scan interval and A/D

integral time

Syntax

XV p1,p2,p3,p4
p1 1 (fixed)
p2 Scan interval mode

NORMAL
FAST

Fast sampling