beautypg.com

App index, Control commands (/as1) – Yokogawa Removable Chassis DX1000N User Manual

Page 130

background image

3-13

IM 04L41B01-17E

Commands

1

2

3

4

5

6

App

Index

Control Commands (/AS1)

To apply settings that you have changed using the basic setting commands, you need to
save the settings using the YE command.

Command

Name

Function

Execution

Mode

Setting Connection

Monitor

Connection

Page

Administrator User

BT

Sets a batch name

O

Yes

Yes

*

No

3-37

BU

Sets a batch comment

O

Yes

Yes

*

No

3-37

MH

Writes a batch text field

O

Yes

Yes

*

No

3-37

UD

Switches the screen

O

Yes

Yes

*

No

3-37

PS

Starts or stops recording

O

Yes

Yes

*

No

3-39

AK

Clears alarm output (acknowledge alarms)

O

Yes

Yes

*

No

3-39

EV

Executes manual sample, takes a snapshot, or

causes a timeout

O

Yes

Yes

*

No

3-39

CL

Executes manual SNTP

O

Yes

Yes

*

No

3-39

CV

Switches between normal and secondary trend

interval

O

Yes

Yes

*

No

3-39

MS

Writes a message (display and write)

O

Yes

Yes

*

No

3-40

BJ

Writes a free message

O

Yes

Yes

*

No

3-40

EJ

Changes the login password

O

Yes

Yes

No

3-40

TL

Starts, stops, resets computation (MATH) or clears

the computation dropout status display

O

Yes

Yes

*

No

3-40

LO

Loads setup data for setting mode

OS

Yes

Yes

*

No

3-41

LI

Saves setup data

S

Yes

Yes

*

No

3-41

CM

Sets communication input data

OSsb

Yes

Yes

Yes

3-41

CE

Sets communication input of an external input

channel

OSsb

Yes

Yes

Yes

3-41

EM

Starts or stops the e-mail transmission function

O

Yes

Yes

*

No

3-41

CU

Recovers Modbus manually

O

Yes

Yes

*

No

3-42

YO

Loads a setup file for basic setting mode

B

Yes

No

No

3-42

IR

Resets a relative timer

O

Yes

Yes

*

No

3-42

MA

Resets a match time timer

O

Yes

Yes

*

No

3-42

CW

Sets an event switch

O

Yes

No

No

3-42

LR

Loads custom display screens

S

Yes

No

No

3-42

LW

Saves custom display screens

S

Yes

No

No

3-43

BQ

User locked ACK (/AS1 advanced security option)

O

Yes

No

No

3-43

EC

Clears setup data (and executes a cold reset; /AS1

advanced security option)

B

Yes

No

No

3-43

EE

Switches out of operation mode (/AS1 advanced

security option)

O

Yes

No

No

3-44

BE

Returns to operation mode (/AS1 advanced security

option)

Ss

Yes

No

No

3-44

Dedicated Barcode Commands (Handled as key input)

BV

Enters a string (can only be used during serial

communication)

ALL

3-44

KE

Performs key operations

OSsb

3-44

BP

Supports login (/AS1 advanced security option)

O

3-44

Dedicated Serial Communication Commands

LL

Logs in through serial communication (/AS1

advanced security option)

ALL

3-44

* Operations are limited by the user privilege settings.

3.2 A List of Commands

This manual is related to the following products: