3.3 Setup Parameters
The measurement range and setup range of parameters used in a command vary
depending on the combination of the command, range, and options.
Parameter Input Example of Measurement Range
The span upper and lower limit parameters of the SR command (input range setting
command) requires all digits including those to the right of the decimal to be entered.
For example, if you want to set the upper limit to 1.0000 V when the measurement range
is -2.0000 V to 2.0000 V, the value is 10000. If you want to set the limit to 0.5000 V, the
value is 5000.
The table below gives configuration examples.
Measurement
Range
Input Type
Parameter
Selectable Range of the
Measurement Range
Specified Range
Parameter
VOLT
20mV
-20.000mV to 20.000mV -10.000mV to 20.000mV -10000 to 20000
/SQRT
2V
-2.0000V to 2.0000V
-2.0000V to 0.5000V
-20000 to 5000
TC
R
0.0 to 1760.0
0.0 to 400.0
0 to 4000
K
-200.0 to 1370.0
-200.0 to 1370.0
-2000 to 13700
RTD
Pt100
-200.0 to 600.0
-10.0 to 500.0
-100 to 5000
DI
LEVEL
0 to 1
0 to 1
0 to 1