• When p6 is set to SEPARATE2, p7 can only
be set to OFF.
Service ports
Syntax
WU p1,p2,p3,p4,p5
p1 Setting type (SERVICEPORT)
p2 FTP service port (1 to 65535)
p3 Web service port (1 to 65535)
p4 SNTP service port (1 to 65535)
p5 Modbus service port (1 to 65535)
Decimal point type
Syntax
WU p1,p2
p1 Setting type (DECIMALPOINT)
p2 Decimal type (POINT, COMMA)
POINT Uses a period for the decimal
point.
COMMA Uses a comma for the decimal
point.
Detailed POP3 settings
Syntax
WU p1,p2,p3
p1 Setting type (POP3)
p2 Delay after accessing POP3 until
transmission (seconds; 0 to 10)
p3 POP3 login method (PLAIN, APOP)
Alarm level settings
Syntax
WU p1,p2
p1 Setting type (ALARM_LEVEL)
p2 Levels (1-2-3-4, 1-4-2-3, 1-4-3-2)
Alarm color settings
Syntax
WU p1,p2,p3,p4,p5
p1 Setting type (ALARM_ COLOR)
p2 Alarm level 1 color (RED, ORANGE,
YELLOW, PINK)
p3 Alarm level 2 color (RED, ORANGE,
YELLOW, PINK)
p4 Alarm level 3 color (RED, ORANGE,
YELLOW, PINK)
p5 Alarm level 4 color (RED, ORANGE,
YELLOW, PINK)
Tag basic setting
Syntax
WU p1,p2
p1 Setting type (TAG)
p2 Tag number usage (USE, NOT)
Basic setting mode menu display settings
Syntax
WU p1,p2
p1 Setting type (MENU)
p2 Basic setting mode menu display (ON, OFF)
Remote contact input operation
Syntax
WU p1,p2,p3,p4,p5,p6,p7,p8,p9
p1 Setting type (REMOTE)
p2 Remote contact 1 input (N.O, N.C)
N.O
Normally opened
N.C
Normally closed
p3 Remote contact 2 input (N.O, N.C)
p4 Remote contact 3 input (N.O, N.C)
p5 Remote contact 4 input (N.O, N.C)
p6 Remote contact 5 input (N.O, N.C)
p7 Remote contact 6 input (N.O, N.C)
p8 Remote contact 7 input (N.O, N.C)
p9 Remote contact 8 input (N.O, N.C)
Description • Use this command on models with the remote
control option.
• On models with the pulse input option, if you
use the remote control input terminal as a
pulse input terminal, the DX counts the rising
pulse edges, independent of the remote
control input settings.
Detailed FTP server settings
Syntax
WU p1,p2
p1 Setting type (FTPSERVER)
p2 Directory output format (MS-DOS, UNIX)
MS-DOS
UNIX
Query
WU[p1]?
Example This is an example for general environment
settings. Display tags, display in English, and
turn remote control off.
WUGENERAL,TAG,ENGLISH,OFF
WE
Sets calibration management
Syntax
WE p1,p2,p3
p1 Whether or not to use calibration
management (USE, NOT)
p2 Alarm (days; 1 to 10)
This setting determines how many days
before the specified calibration due date to
start displaying notifications.
p3 Renotification interval (10min, 30min, 1h,
8h, 24h)
Query
WE?
Example
Use the calibration management function. Start
notifications a day before the calibration due
date and continue producing notifications every 8
hours afterwards.
WEUSE,1,8h
Description • p2 and p3 are valid when p1 is set to USE.
• You can make settings with this command on
models with the /CC1 input calibration option.
BI
Configures signature settings
(/AS1 advanced security option)
Syntax
BI p1,p2,p3,p4
p1 Process type (BATCH, CONTINUE)
p2 Signature on the DX (OFF, SIGNIN1,
SIGNIN1+2, SIGNIN1+2+3)
p3 Signature at batch stop (ON, OFF)
p4 FTP transfer at signing (ON, OFF)
Query
BI ?
Example Set the command so that the process type is
BATCH, only signatures 1 and 2 are used on the
3.6 Basic Setting Commands