3.4 Setting Commands
invalid, the DX returns “1.”
• If p4 = MESSAGE and p7 or p8 is invalid, the
DX returns p7 = “1” or p8 = “1.”
Examples are given below.
p1 through p3 are indicated by an ellipsis. The
set values of invalid parameters are bolded.
• When the multi batch function is invalid:
TU...,MEMORYSTART/STOP,
ALL
TU...,DISPLAYGROUPCHANGE,2,
1
TU...,MESSAGE,5,ALL,
1,1
TU...,MESSAGE,5,SELECT,10,
1
• When the multi batch function is valid
TU...,MESSAGE,5,ALL,
1,3
Example Execute memory start with the remote control
input (terminal 1).
TUREMOTE,1,MEMORYSTART
Description • Set various numbers (relay number, internal
switch number, etc.) by referring to the table in
section 3.3.
• You cannot select some of the p4 (action type)
settings depending on the p2 (event type)
setting.
• You cannot select some of the p4 (action type)
settings depending on other DX settings or
depending on the installed options.
• The p4=ALARMDISPLAYRESET setting is
valid when the annunciator function is enabled
and the annunciator sequence is set to ISA-M.
• Set the batch group number by referring to the
table in section 3.3.
• When multi batch /BT2 is in use, p4 is set
to MATHRESET, and p5 is set to ALL, the
calculated values for all computation channels
are reset.
• An event that has “-OFF” attached to it
responds to the logical negation of the
corresponding event that does not have “-OFF”
attached to it. The actions and settings that
the event can support are the same as those
that the corresponding event that does not
have “-OFF” attached to it can support.
• On models with the /AS1 advanced security
option, you cannot set p4 to TRIGGER or
PANELLOAD.
SK
Sets a constant
Syntax
SK p1,p2
p1 Constant number
p2 Constant (-9.9999E+29 to -1.0000E-30, 0,
1.0000E-30 to 9.9999E+29, 5 significant
digits)
Query
SK[p1]?
Example Set the constant in constant number K01 to
1.0000E-10.
SKK01,1.0000E-10
Description • You can use this command on models with the
/M1 or /PM1 math option.
• You cannot use this command while recording
(memory sampling) or computation is in
progress. When using the /BT2 multi batch
option, you cannot use this command if any
of the batch groups is recording (memory
sampling).
• Set p1 by referring to the table in section 3.3.
SI
Sets the rolling average function
of a computation channel
Syntax
SI p1,p2,p3,p4
p1 Computation channel number
p2 Moving average (ON, OFF)
p3 Sampling interval (1S, 2S, 3S, 4S, 5S, 6S,
10S, 12S, 15S, 20S, 30S, 1MIN, 2MIN,
3MIN, 4MIN, 5MIN, 6MIN, 10MIN, 12MIN,
15MIN, 20MIN, 30MIN, 1H)
p4 Number of samples (1 to 1500)
Query
SI[p1]?
Example Turn on the rolling average function of
computation channel 107, set the sampling
interval to 1 minute, and the number of samples
to 20.
SI107,ON,1MIN,20
Description • You can use this command on models with the
/M1 or /PM1 math option.
• Do not set p3 or p4 when p2 is set to OFF.
• Set the sampling interval to a value greater
than the scan interval.
SJ
Sets a TLOG timer
Syntax
SJ p1,p2,p3,p4,p5
p1 Computation channel number
p2 Timer number
p3 Conversion of the unit of time for TLOG.
SUM computation
OFF
Do not convert.
/S
Converts as though the physical
values are integrated in units of
seconds.
/MIN
Converts as though the physical
values are integrated in units of
minutes.
/H
Converts as though the physical
values are integrated in units of
hours.
p4 Reset (ON, OFF)
p5 Timer type
TIMER
Timer
MATCHTIMETIMER
Match time timer
Query
SJ[p1]?
Example Assign timer 1 to computation channel number
110. Do not convert the unit of time and enable
the reset setting.
SJ110,1,OFF,ON,TIMER