3-20

IM 04L41B01-17E

• For parameters p7, p8, and p9, either set all

three parameters or omit all three parameters.

When Setting Channels to Square Root

Computation

Syntax

SR p1,p2,p3,p4,p5,p6,p7,p8,p9,p10,
p11
p1 Measurement channel number
p2 Setting type (SQRT)
p3 Measurement range
p4 Span lower limit
p5 Span upper limit
p6 Scaling lower limit (-30000 to 30000)
p7 Scaling upper limit (-30000 to 30000)
p8 Scaling decimal place (0 to 4)
p9 Unit (up to 6 characters)
p10 Low-cut function (OFF, ON)
p11 Low-cut point (0 to 50)

Query

SR[p1]?

Example Convert the DC voltage measured on channel

001 to an amount of flow using the square root
computation. Set the measurement range to 6 V,
the span lower limit to 1 V, the span upper limit to
5 V, the scaling lower limit to 10.0 m

3

/s, and the

scaling upper limit to 100.0 m

3

/s.

SR001,SQRT,6V,1000,5000,100,1000,1,
m3/s

Description • You cannot use this command while recording

(memory sampling) or computation is in
progress. When using the /BT2 multi batch
option, you cannot use this command if any
of the batch groups is recording (memory
sampling).

• Set p1 and p3 by referring to the table in

section 3.3.

• For parameters p4 and p5, enter values with

five digits or less excluding the decimal point.

• For parameters p6, p7, and p8, either set all

three parameters or omit all three parameters.

For 1-5V DC Voltage Input

Syntax

SR p1,p2,p3,p4,p5,p6,p7,p8,p9,p10

p1 Measurement channel number
p2 Input type (1-5V)
p3 Measurement range (1-5V)
p4 Span lower limit (800 to 5200)
p5 Span upper limit (800 to 5200)
p6 Scaling lower limit (-30000 to 30000)
p7 Scaling upper limit (-30000 to 30000)
p8 Scaling decimal place (0 to 4)
p9 Unit (up to 6 characters)
p10 Low-cut function (ON, OFF)

Query

SR[p1]?

Example Set the channel 005 input type to 1-5V, the span

lower limit to 1 V, the span upper limit to 5 V, and
turn the 1-5V low-cut function ON.
SR005,1-5V,1-5V,1000,5000,,,,,ON

Description • You cannot use this command while recording

(memory sampling) or computation is in
progress. When using the /BT2 multi batch
option, you cannot use this command if any
of the batch groups is recording (memory
sampling).

• Set p1 by referring to the table in section 3.3.
• For parameters p4 and p5, enter values with

four digits or less excluding the decimal point.

• For parameters p6, p7, and p8, either set all

three parameters or omit all three parameters.

SO

Sets a computing equation

Syntax

SO p1,p2,p3,p4,p5,p6,p7
p1 Computation channel number
p2 Computation (ON, OFF)
p3 Computing equation (up to 120 characters)
p4 Span lower limit (-9999999 to 99999999)
p5 Span upper limit (-9999999 to 99999999)
p6 Span decimal place (0 to 4)
p7 Unit (up to 6 characters)

Query

SO[p1]?

Example Compute the sum of channels 001 and 002

using channel 106. Set the span lower limit to
-10.0000, the span upper limit to 15.0000, and
the unit to V.
SO106,ON,001+002,-100000,150000,4,V

Description • You can use this command on models with the

/M1 or /PM1 math option.

• You cannot use this command while recording

(memory sampling) or computation is in
progress. When using the /BT2 multi batch
option, you cannot use this command if any
of the batch groups is recording (memory
sampling).

• For details on computing equations, see the

DX1000/DX1000N or DX2000 User’s Manual.

• Set p1 by referring to the table in section 3.3.
• For parameters p4 and p5, enter values with

seven digits or less, excluding the decimal, for
negative numbers and with eight digits or less
for positive numbers.

• For parameters p4, p5, and p6, either set all

three parameters or omit all three parameters.

ER

Sets the range of an external

input channel

Syntax

ER p1,p2,p3,p4,p5,p6
p1 External input channel number
p2 External input channel (ON, OFF)
p3 Span lower limit (-30000 to 30000)
p4 Span upper limit (-30000 to 30000)
p5 Decimal place (0 to 4)
p6 Unit (up to 6 characters)

Query

ER[p1]?

3.4 Setting Commands