6 basic setting commands, 6 basic setting commands -45, App index – Yokogawa Removable Chassis DX1000N User Manual
Page 162: Wu sets the environment
3-45
Commands
IM 04L41B01-17E
1
2
3
4
5
6
App
Index
p5 Reconfirmation of the new password to
use if the current one has expired (up to 20
characters)
This parameter is meaningless if the
current password has not yet expired. This
parameter can be omitted.
Example Log in as user a (whose user ID is “aaaa” and
whose password is “aaaaaa”), start computation,
and execute memory start.
LLa,aaaa, aaaaaa;TL0;PS0
Description • This command can be used if the login
function has been enabled (by an
administrator).
• After the LL command, use sub delimiters to
make a list of commands to execute.
• You log into the DX when you execute this
command, and you are automatically logged
out after the command is executed.
• The LL command communication responses,
including those for errors, are the same as
those for other commands.
3.6 Basic Setting Commands
WU
Sets the environment
Settings
GENERAL, BATCH, DISPLAY, MESSAGE,
INPUT, ALARM, SECURITY, MEDIA, MATH,
REPORT, SERVICEPORT, DECIMALPOINT,
POP3, ALARM_LEVEL, ALARM_ COLOR,
TAG, MENU, REMOTE, and FTPSERVER
General environment settings
Syntax
WU p1,p2,p3,p4
p1 Setting type (GENERAL)
p2 Selects tag or channel number
TAG
Tag
CHANNEL Channel number
p3 Language
ENGLISH
JAPANESE
CHINESE
GERMAN
FRENCH
p4 Remote control ID (OFF, 0 to 31)
Batch settings
Syntax
WU p1,p2,p3,p4,p5
p1 Setting type (BATCH)
p2 Batch function (OFF, ON, MULTIBATCH)
OFF
Disables the batch function
ON
Enables the batch function
MULTIBATCH
Enables the multi batch
function
p3 Number of lot number digits (OFF, 4, 6, 8)
p4 Auto increment (ON, OFF)
p5 Number of batch groups (DX1000: 2 to 6.
DX2000: 2 to 12)
Description • Parameters p3 and p4 are valid when p2 is set
to ON.
• Parameters p3, p4, and p5 are valid when p2
is set to MULTIBATCH.
Display settings
Syntax
WU p1,p2,p3,p4
p1 Setting type (DISPLAY)
p2 Trend type
T-Y
T-Y display
CIRCULAR Circular display
p3 Partial expansion(OFF, ON)
p4 Trend interval switching (OFF, ON)
Description • Parameters p3 and p4 are valid when p2 is set
to T-Y.
• When multi batch is in use, p4 is fixed at OFF.
Message settings
Syntax
WU p1,p2,p3,p4
p1 Setting type (MESSAGE)
3.5 Control Commands / 3.6 Basic Setting Commands