App index – Yokogawa Removable Chassis DX1000N User Manual
Page 176
3-59
Commands
IM 04L41B01-17E
1
2
3
4
5
6
App
Index
WG
Sets an IP address that is
allowed to connect via Modbus
Syntax
WG p1,p2
p1 Registration number (1 to 10)
p2 Whether or not to register (ON, OFF)
p3 IP address (0.0.0.0 to 255.255.255.255)
Query
WG[p1]?
Example Allow connection from 192.168.111.24. Use
registration number 1.
WG1,ON,192.168.111.24
Description This command is valid when the Modbus
connection limitation is placed (WF command).
WJ
Sets the FTP transfer wait time
Syntax
WJ p1,p2
p1 Display data and event data [minutes] (0 to
120)
p2 Reports [minutes] (0 to 120)
Query
WJ?
Example Set the FTP transfer wait time for report data to
30 minutes. Do not set a wait time for display
data and event data.
WJ0,30
WQ
Sets PROFIBUS-DP
Syntax
WQ p1
p1 Node address (0 to 125)
Query
WQ ?
Example Set the node address to 121.
WQ121
Description • You can use this command on models with the
/CP1 PROFIBUS-DP option.
XE
Activates basic settings
Syntax
XE p1
p1 Whether or not to save settings (STORE,
ABORT)
Example Save basic settings.
XESTORE
Description • To activate the settings you have changed
using basic setting commands, you must use
the XE command to save the settings. Be sure
to use the XE command to save the settings
before switching the execution mode back to
operation. If you do not save the settings and
change the execution mode back to operation,
the DX returns to the previous settings.
• This command is invalid on models with the
/AS1 advanced security option.
YE
Activates basic settings (cold
reset)
Syntax
YE p1
p1 Whether or not to activate settings
STORE Save basic settings and restart
ABORT Restart without saving basic
settings
Example Saves basic settings and restart.
YESTORE
Description If the settings are changed during memory
sampling in basic setting mode, a cold reset is
not executed. The login status is sustained.
3.6 Basic Setting Commands