Yokogawa Removable Chassis DX1000N User Manual
Page 240
6-14
IM 04L41B01-17E
Register
Description
Supplementary Information
Type
Access
Simultaneous
Access
Write
Read
410401 to
410402
Batch 9 lot number
Valid range: 0 to 99999999
INT32_L
R/W
410403 to
410420
Batch 9 batch number Up to 18 registers (up to 35 characters with '\0'
termination).
The batch number must be 32 characters or less.
STR36
R/W
410421 to
410450
(Reserved) batch 9
-
-
-
410451 to
410452
Batch 10 lot number
Valid range: 0 to 99999999
INT32_L
R/W
410453 to
410470
Batch 10 batch number Up to 18 registers (up to 35 characters with '\0'
termination).
The batch number must be 32 characters or less.
STR36
R/W
410471 to
410500
(Reserved) batch 10
-
-
-
410501 to
410502
Batch 11 lot number
Valid range: 0 to 99999999
INT32_L
R/W
410503 to
410520
Batch 11 batch number Up to 18 registers (up to 35 characters with '\0'
termination).
The batch number must be 32 characters or less.
STR36
R/W
410521 to
410550
(Reserved) batch 11
-
-
-
410551 to
410552
Batch 12 lot number
Valid range: 0 to 99999999
INT32_L
R/W
410553 to
410570
Batch 12 batch number Up to 18 registers (up to 35 characters with '\0'
termination).
The batch number must be 32 characters or less.
STR36
R/W
410571 to
410600
(Reserved) batch 12
-
-
-
410601
Preset message writing Message number (1 to 100)
INT16
W
410602
Message write destination
• When the multi batch function is not in use
0: All groups. 1 to 36: Specified group number.
• When the multi batch function is in use
0: All groups of a specified batch number
(410603)
1 to 12: Specified group number
INT16
W
410603
Batch number designation for multi batch: 1 to 12
(Valid only when the multi batch function is
available. Any value when the multi batch function
is not available)
INT16
W
410604 to
410610
(Reserved) Preset
message
-
-
-
6.3 Modbus Protocol Specifications