7 output commands (control), 7 output commands (control) -60, Bo sets the output byte order – Yokogawa Removable Chassis DX1000N User Manual

Page 177: If sets status filters, Cb sets the data output format

background image

3-60

IM 04L41B01-17E

3.7 Output Commands

(Control)

BO

Sets the output byte order

Syntax

BO p1
p1 Byte order

0

Outputs data MSB first.

1

Outputs data LSB first.

Query

BO?

Example Output data MSB first.

BO0

Description This command applies to the byte order of

numeric data for BINARY output.

CS

Sets the check sum (can

only be used during serial

communications)

Syntax

CS p1
p1 Checksum usage

0

Do not calculate (value fixed at
zero)

1

Calculate

Query

CS?

Example Enable (Calculate) the checksum.

CS1

Description You can use this command only for serial

communications.

IF

Sets status filters

Syntax

IF p1,P2
p1 Filter values for status information numbers

1 to 4

(0.0.0.0 to 255.255.255.255)

p2 Filter values for status information numbers

5 to 8

(0.0.0.0 to 255.255.255.255)

Query

IF?

Example Set the status filter values to 1.0.4.0 and

255.127.63.31.
IF 1.0.4.0,255.127.63.31

Description For details, see chapter 5.

CB

Sets the data output format

Syntax

CB p1
p1 Output format

0

Normal output (includes data from
channels set to SKIP and OFF)

1

Do not output data from channels
set to SKIP or OFF

Query

CB?

Example Set the output format to normal output.

CB0

Description • This setting is separate for each connection.

• This command only affects the communication

section and does not affect the front panel
settings.

• Effective range of commands

Output information

Corresponding

command

Instantaneous data output (binary)

FD1, FF

Instantaneous data output (ASCII)

FD0

Decimal place information (ASCII)

FE1

Setup channel information (binary)

FE5

Configured alarm information (binary) FE6

CC

Disconnects the Ethernet

connection (can only be used for

Ethernet communications)

Syntax

CC p1
p1 Disconnection (0)

Example Disconnect the connection.

CC0

Note

Initialization of settings specified using the BO, CS, IF, and

CB commands

• Serial communications

Settings specified using the BO, CS, IF, and CB commands

are reset to the following default values when you reset the DX

(when you turn the DX off and then back on or when you exit

from basic setting mode).

• Output byte order, checksum, output format: 0

• Status filter: 255.255.255.255

If you reset the DX, you must set these values again.

• Ethernet communications

Settings specified using the BO, IF, and CB commands

are reset to their default values when you disconnect the

connection to the DX. After reconnecting to the DX, set these

values again.

3.7 Output Commands (Control)