beautypg.com

10 using the modbus client function, 10 using the modbus client function -56, Setting the modbus client – Yokogawa Removable Chassis DX1000N User Manual

Page 64

background image

1-56

IM 04L41B01-17E

1.10 Using the Modbus Client Function

The DX is used as a Modbus client.
For the Modbus specifications, see section 6.3.

Setting the Modbus Client

Carry out the steps below to enable the DX to read the data of another device or write
data to another device using Modbus.
◊ Press

MENU (to switch to setting mode), hold down FUNC for 3 s (to switch to basic

setting mode), and select the

Menu tab > Communication (Ethernet) > Modbus

client.

Basic settings

Destination server settings

Transmitted command settings

Basic settings

• Read cycle

Set the read cycle to 125m, 250m, 500m, 1, 2, 5, or 10s.

• Retry interval

Set the interval for retrying the connection when the connection is interrupted for some

reason. Select Off, 10, 20, or 30 s, 1, 2, 5, 10, 20, or 30 min, or 1 h. When Off is
selected, the connection is not retried. The communication stops if the communication
fails.

Destination server settings

• Server number

Select 1 to 16 for the server registration numbers to be configured.

• Port

Enter the port number in the range of 0 to 65535 for the selected server. The default

value is 502.

• Modbus server name

Set the destination Modbus server name using up to 64 alphanumeric characters.

• If the DNS is used, you can set the host name as a server name.
• You can also set the IP address. In this case, the DNS is not required.

This manual is related to the following products: