3-24
IM 04L41B01-17E
display area.
• The zone size must be at least 5%.
• Set the upper zone boundary position greater
than the lower zone boundary position.
SP
Sets a partial expanded display
Syntax
SP p1,p2,p3,p4
p1 Measurement, computation, or external
input channel number
p2 Partial expanded display (ON, OFF)
p3 Boundary position (1 to 99) [%]
p4 Boundary value
Query
SP[p1]?
Example Partially expand the display of channel 001. Set
the boundary position to 25% and the boundary
value to 1.00 V.
SP001,ON,25,100
Description • You can specify computation channels on
models with the /M1 or /PM1 math option.
You can specify external input channels on
models with the /MC1 external input channel
option.
• For a channel whose input range is set to
SKIP (using the SR command), p2 cannot be
set to ON.
• For a channel whose computation channel is
turned off (using the SO command), p2 cannot
be set to ON.
• For a channel whose external input channel
is set to OFF (using the ER command), p2
cannot be set to ON.
• Set p3 as a percentage of the range defined
by the span upper and lower limits (scale
upper and lower limits when scaling is
enabled).
• Set p4 to a value from (span upper limit – 1) to
(span lower limit + 1). If scaling is enabled, set
p4 to a value from (scaling lower limit – 1) to
(scaling upper limit + 1).
• The decimal place and the number of digits
are the same as those for the span or scaling
settings (see the SR command).
• You can use this command (includes the
query) when the partial expanded display
function is set to USE (using the XU
command).
• You cannot use this command if the partial
expanded display range does not exist (for
example when the span range is 1).
ST
Sets a tag
Syntax
ST p1,p2,p3
p1 Measurement, computation, or external
input channel number
p2 Tag comment (up to 32 characters)
p3 Tag number (up to 16 characters)
Query
ST[p1]?
Example Set the channel 002 tag (tag comment) to TAG2.
ST002,TAG2
Description • For the characters that you can use for tags,
see appendix 3, “ASCII Character Codes.”
Note that you cannot use semicolons or
commas.
• You can specify computation channels on
models with the /M1 or /PM1 math option. You
can specify external input channels on models
with the /MC1 external input channel option.
• Parameter p3 is invalid when you are not
using the tag number. The DX returns the
previous value in response to a query.
SX
Sets a display group (release
number 2 or earlier)
Syntax
SX p1,p2,p3,p4
p1 Display group number
p2 Display group (ON, OFF)
p3 Display group name (up to 16 characters)
p4 Channel configuration
Query
SX[p1]?
Example Assign channels 001, 003, 004 to 006 to group
number 1 and name the group GROUP2.
SX1,ON,GROUP2,001.003.004-006
Assign channels by using periods to separate
each channel or a hyphen to specify a range of
channels.
Description • For the characters that you can use for group
names, see appendix 3, “ASCII Character
Codes.” Note that you cannot use semicolons
or commas.
• If you are using the multi batch feature /BT2,
this command affects batch group 1.
• If you are using the multi batch feature /BT2
and batch group 1 is recording (memory
sampling), you cannot use this command.
• Set p1 by referring to the table in section 3.3.
SL
Sets a trip line (release number 2
or earlier)
Syntax
SL p1,p2,p3,p4,p5,p6
p1 Display group number
p2 Trip line number (1 to 4)
p3 Trip line display (ON, OFF)
p4 Display position (0 to 100) [%]
p5 Display color (RED, GREEN, BLUE,
B.VIOLET, BROWN, ORANGE,
Y.GREEN, LIGHTBLUE, VIOLET, GRAY,
LIME, CYAN, DARKBLUE, YELLOW,
LIGHTGRAY, PURPLE, BLACK, PINK,
L.BROWN, L.GREEN, DARKGRAY, OLIVE,
DARKCYAN, S.GREEN)
p6 Line width (1, 2, 3)
3.4 Setting Commands