1.9 Using the Modbus Server Function
The DX is used as a Modbus server.
For the Modbus specifications, see section 6.3.
Setting the Modbus Server
Carry out the steps below to enable another device to read the DX data or write data to
the DX using Modbus.
◊ Press
MENU (to switch to setting mode), hold down FUNC for 3 s (to switch to basic
setting mode), and select the
Menu tab > Communication (Ethernet) > Server >
Server modes.
• Modbus
For the Modbus item under Server, select
Use or Not (don’t use).
◊ Press
MENU (to switch to setting mode), hold down FUNC for 3 s (to switch to basic
setting mode), and select the
Menu tab > Communication (Ethernet) > Server >
Allowed Modbus clients.
• Use/Not
To place a limitation on the IP addresses that can connect to the DX Modbus server,
select
Use. Only the IP addresses specified here can connect to the DX Modbus
server. To not place a limitation, select
Not.
• Client number
You can register up to 10 IP addresses. Select the client number from 1 to 10.
• On/Off
To allow connections, select
On.
• Allowed IP Address
Enter the IP address in the range of 0.0.0.0 to 255.255.255.255. You cannot enter a
host name.