Configuring the POP3 Server Connection (Release number 3 or later)

Specify how the DX operates when it connects to a POP server.
◊ Press

MENU (to switch to setting mode), hold down FUNC for 3 s (to switch to basic

setting mode) and select the

Environment tab > Communication > POP3 Details.

Send delay [seconds]

Enter the delay between a POP3 server authentication and the transmission in the range
of 0 to 10 seconds.

POP3 Login

To encrypt the password when logging into the POP3 server, select APOP. To send it in
plain text, select PLAIN.

E-mail Test

◊ Press

FUNC and select E-mail test > Recipient1 or Recipient2.

You can send a test e-mail to check the e-mail settings.

Starting/Stopping the E-mail Transmission

Starting the e-mail transmission

◊ Press

FUNC and select E-Mail START.

The e-mail transmission function is enabled.

Stopping the e-mail transmission

◊ Press

FUNC and select E-Mail STOP.

The e-mail transmission function is disabled. Unsent e-mail messages are cleared.

E-mail retransmission

If the e-mail transmission fails, the message is retransmitted up to three times at 30-s,
1-minute, or 3-minute intervals. If retransmission fails, the e-mail message is discarded.