Yokogawa Removable Chassis DX1000N User Manual
Page 155
3-38
IM 04L41B01-17E
Description On models with the /AS1 advanced security
option, use the BE command to return to
operation mode.
To switch to one panel display
Syntax
UD p1,p2,p3
p1 Screen type (1)
p2 Display item
TREND
Trend display
DIGITAL Digital display
BAR
Bar graph display
OVERVIEW Overview display
(alarm indicator)
ALARM
Alarm summary display
MESSAGE Message summary display
MEMORY Memory summary display
MODBUS-M Modbus master status display
MODBUS-C Modbus client status display
RELAY
Relay status display
REPORT Report display
HISTRICAL Historical trend display
COLUMN_BAR
Stacked bar graph
INTERNAL1 to INTERNAL3
Custom display,
internal 1 to 3
EXTERNAL1
to
EXTERNAL25
Custom display,
external 1 to 25
ANNUNCIATOR
Annunciator display
EVENT_SWITCH
Event switch status display
p3 Display group number
Example Set the display to one screen trend, and set the
number of the group to display in the screen to 4.
UD1,TREND,4
Description • The setting p2=MODBUS-M is only valid if the
serial interface protocol is set to MODBUS-M.
• The setting p2=REPORT is only valid on
models with the /M1 or /PM1 math option.
• When multi batch /BT2 is in use, there are
limitations on the screens that the DX can
switch to depending on the screen mode.
Batch overview mode
Overview display, Modbus master status
display, Modbus client status display, relay
status display, report display, stacked bar
graph, custom display, annunciator display,
and event switch status display
Batch single mode
Trend display, digital display, bar graph
display, overview display, alarm summary
display, message summary display, memory
summary display, historical trend display, and
custom display
• When multi batch /BT2 is in use, you cannot
specify a display group that does not belong
to the currently displayed batch group.
• Set parameter p3 by referring to the table in
section 3.3.
• The setting p2=ANNUNCIATOR is only valid
when the annunciator mode is turned on (by
the WU command).
To switch to four panel display
Syntax
UD p1,p2,p3,p4,p5,p6,p7,p8,p9
p1 Screen type (2)
p2 Screen 1 type (see SY; sets a screen group)
p3 Number of the group to display in screen 1
p4 Screen 2 type (see SY; sets a screen group)
p5 Number of the group to display in screen 2
p6 Screen 3 type (see SY; sets a screen group)
p7 Number of the group to display in screen 3
p8 Screen 4 type (see SY; sets a screen group)
p9 Number of the group to display in screen 4
Example Assign group 1 to screen 1, group 2 to screen 2,
group 3 to screen 3, group 4 to screen 4, and set
the screen type of all screens to trend.
UD2,TREND,1,TREND,2,TREND,3,TREND,4
Description • You can use this command on the DX2000.
• When multi batch /BT2 is in use, you cannot
specify a display group that does not belong
to the currently displayed batch group. You
cannot use this command in batch overview
mode.
To display a specific four panel display
Syntax
UD p1,p2
p1 Display type (3)
p2 Four panel configuration number
0
Displays the four panel
configuration that you specify
directly.
1 to 4 Displays a four panel configuration
that you set using SY (sets a
screen group).
Description • You can use this command on the DX2000.
• When multi batch /BT2 is in use, you cannot
use this command in batch overview mode.
To switch the operation screen
Syntax
UD p1,p2,p3,p4,p5,p6,p7,p8,p9,p10
p1 Screen type (4)
p2 Automatic display switching (ON, OFF)
p3 Switches between all channel display and
group display (ALL, GROUP)
p4 Scale display (ON, OFF)
p5 Digital display (ON, OFF)
p6 Message display options
1
Normal display
2
List display
p7 Trend space (ON, OFF)
p8 Auto zone (ON, OFF)
p9 Fine grid (ON, OFF)
3.5 Control Commands