beautypg.com

Yokogawa Removable Chassis DX1000N User Manual

Page 100

background image

2-6

IM 04L41B01-17E

• XON-XON

• Data transmission control
Software handshaking is performed between the DX and the PC. When an

“X-OFF” code is received while sending data to the PC, the DX stops the data
transmission. When the DX receives the next “X-ON” code, the DX resumes the
data transmission. The CS signal received from the PC is ignored.

• Data reception control
Software handshaking is performed between the DX and the PC. When the free

area of the received buffer decreases to 1537 bytes, the DX sends an “X-OFF”
code. When the free area increases to 511 bytes, the DX sends an “X-ON” code.

RS = True (fixed).

• XON-RS

• Data transmission control
The operation is the same as with XON-XON.
• Data reception control
Hardware handshaking is performed between the DX and the PC. When the free

area of the received buffer decreases to 1537 bytes, the DX sets “RS=False.”
When the free area increases to 511 bytes, the DX sets “RS=True.”

• CS-RS

• Data transmission control
Hardware handshaking is performed between the DX and the PC. When the

CS signal becomes False while sending data to the PC, the DX stops the data
transmission. When the CS signal becomes True, the DX resumes the data
transmission. The “X-OFF” and “X-ON” signals are treated as data.

• Data reception control
The operation is the same as with XON-RS.

Note

• The PC program must be designed so that the received buffers of both the DX and the PC

do not become full.

• If you select XON-XON, send the data in ASCII format.

2.3 Connecting the DX

This manual is related to the following products: