How to use – Yokogawa Removable Chassis DX1000N User Manual

Page 244

background image

6-18

IM 04L41B01-17E

How to Use

Item

Description

Data type STRnn

Registers in which ASCII codes are entered starting with the specified

register. It is terminated with a NULL character (\0).
The number of characters that can be entered that includes the NULL

character is indicated in the nn section.

Example of setting the batch number (STR36 type) of batch group 1 to “ABCD”
"**" denotes any value.

Register

Value to Write

Hexadecimal Notation

410003

'A''B'

(4142H)

410004

'C''D'

(4344H)

410005

'\0'*

(00**H)

410006 to
410020

**

(****H)

Write the entire character string using one command.
In the above example, registers 410003 to 410005 must be written using one

command.
A zero is read when you read a write-only register.

Lot number

• Access the registers two registers at a time.
• You can only access from the first register.
• On models without the multi batch function (/BT2 option) or on models

with the multi batch function (/BT2 option) but with the multi batch

function disabled, if you access a lot number of a batch group, an error

occurs.

Batch number

• You can only access from the first register.
• On models without the multi batch function (/BT2 option) or on models

with the multi batch function (/BT2 option) but with the multi batch

function disabled, if you access a batch number of a batch group, an

error occurs.

Message

• You can only write from the first register.
• A message is written using one command. In other words, write to

registers 410601 to 410603 using one command. On models without

the multi batch function, you only have to write to registers 410601 and

410602 instead.

On models without the multi batch function, the message write destination

can be omitted (write only to 410601). If you omit it, the operation is the same

as when all groups are specified.

Free message

• You can only write from the first register.
• A free message is written using one command.
If you omit the free message section, an all-space message is written.
On models without the multi batch function, the message write destination

and subsequent registers can be omitted (write only to 410611). If you omit

them, an all-space message is written to every group.
Example: To write the free message "ABCD" to all display groups in batch

group number 4 using message number 10, write the values in the

following table using one command. "**" denotes any value.

Register

Value to Write

Hexadecimal Notation

410611

10

(000AH)

410612

0

(0000H)

410613

4

(0004H)

410614

'A''B'

(4142H)

410615

'C''D'

(4344H)

410616

'\0'*

(00**H)

Computation reset

On models without the multi batch function (/BT2 option) or on models

with the multi batch function (/BT2 option) but with the multi batch function

disabled, if you access computation reset of a batch group, an error occurs.

6.3 Modbus Protocol Specifications