W a t l o w S e r i e s P D

92

C h a p t e r 9 D e v i c e C o n f i g T a b l e

Parameter Name

and Description

Web Page

Your

Settings

Range

Default

Modbus*

(Read/write and

scaling)

Output 1 - Analog TypeSelect analog output type.,Configuration Output 1,,Voltage (0)Current (1),Voltage (0),409 (R/W)
Output 1 - mA Low ScaleSet unit value for low end of current range. This setting determines range of output.,Configuration Output 1,,0 to
20000,4000,410-411 (R/W) (/1000)
Output 1 - mA High ScaleSet unit value for high end of current range. This setting determines range of output.,Configuration Output 1,,0
to 20000,20000,412-413 (R/W) (/1000)
Output 1 - V Low ScaleSet unit value for low end of voltage range. This setting determines range of output.,Configuration Output 1,,0 to
10000,0,414-415 (R/W) (/1000)
Output 1 - V High ScaleSet unit value for high end of voltage range. This setting determines range of output.,Configuration Output 1,,0 to
10000,10000,416-417 (R/W) (/1000)
Output 1 - Retransmit SourceSelect which source output 1 will retransmit.,Configuration Output 1,,Process Value 1 (0)Process Value 2
(2)Set Point 1 (1)Set Point 2 (3),Process Value 1 (0),422 (R/W)
Output 1 - Retransmit Low ScaleSet low end of current or voltage range to retransmit.,Configuration Output 1,,-2000000200 to
2000000200,-2000000200,423-424 (R/W) (/1000)
Output 1 - Retransmit High ScaleSet high end of current or voltage range to retransmit.,Configuration Output 1,,-2000000200 to
2000000200,2000000200,425-426 (R/W) (/1000)

Output 1 - StateDisplay state of output.,Trend Information,,Inactive (0)Active (1),Inactive (0),397 (R)

Output 1 - Analog Type

Select analog output type.

Configuration Output 1

Voltage (0)
Current (1)

Voltage (0)

409 (R/W)

Output 1 - Current Low Scale

Set unit value for low end of
current range. This setting
determines range of output.

Configuration Output 1

0 to 20000 units

4000

410-411 (R/W)
(/1000)

Output 1 - Current High Scale

Set unit value for high end of
current range. This setting
determines range of output.

Configuration Output 1

0 to 20000 units

20000

412-413 (R/W)
(/1000)

Output 1 - Voltage Low Scale

Set unit value for low end of
voltage range. This setting
determines range of output.

Configuration Output 1

0 to 10000 units

0

414-415 (R/W)
(/1000)

Output 1 - Voltage High Scale

Set unit value for high end of
voltage range. This setting
determines range of output.

Configuration Output 1

0 to 10000 units

10000

416-417 (R/W)
(/1000)

Output 1 - Retransmit Source

Select which source Output 1
will retransmit.

Configuration Output 1

Process Value 1 (0)
Process Value 2 (2)
Set Point 1 (1)
Set Point 2 (3)

Process Value
1 (0)

422 (R/W)

Output 1 - Retransmit

Low Scale

Set low end of the current or
voltage range for the retrans-
mit signal.

Configuration Output 1

-2000000200 to 2000000200
degrees or units

-2000000200

423-424 (R/W)
(/1000)

Output 1 - Retransmit

High Scale

Set high end of the current or
voltage range for the retrans-
mit signal.

Configuration Output 1

-2000000200 to 2000000200
degrees or units

2000000200

425-426 (R/W)
(/1000)

Output 1 - Retransmit Offset

Set the offset value for the re-
transmit signal.

Configuration Output 1

-9999000 to 9999000 de-
grees or units

0

427-428 (R/W)
(/1000)

Output 1 - State

Display state of output.

Monitor Device

Inactive (0)
Active (1)

Inactive (0)

397 (R)