Watlow Series PD User Manual
Page 81
W a t l o w S e r i e s P D
■
79
■
C h a p t e r 9 D e v i c e C o n f i g T a b l e
Device Configuration > Control Loops > Loop 1 > PID Set 2
Loop 1 - PID Set 2, Indirect IntegralPID Set 2 - Set the heat (indirect) integral in minutes per repeat.,Configuration Multiple PID Sets 1,,0
to 99990,0,697-698 (R/W) (/1000)
Loop 1 - PID Set 2, Indirect DerivativePID Set 2 - Set the heat (indirect) derivative time in minutes.,Configuration Multiple PID Sets 1,,0 to
9990,0,699-700 (R/W) (/1000)
Loop 1 - PID Set 2, Indirect Dead BandPID Set 2 - Set the offset of the heat (indirect) proportional band from set point in process
units.,Configuration Multiple PID Sets 1,,0 to 999000,0,693-694 (R/W) (/1000)
Loop 1 - PID Set 2, Direct Prop BandPID Set 2 - Set the cool (direct) proportional band from set point in process units.,Configuration Multi-
ple PID Sets 1,,1000 to 999000,25000,703-704 (R/W) (/1000)
Loop 1 - PID Set 2, Direct IntegralPID Set 2 - Set the cool (direct) integral in minutes per repeat.,Configuration Multiple PID Sets 1,,0 to
99990,0,705-706 (R/W) (/1000)
Loop 1 - PID Set 2, Direct DerivativePID Set 2 - Set the cool (direct) derivative time in minutes.,Configuration Multiple PID Sets 1,,0 to
9990,0,707-708 (R/W) (/1000)
Loop 1 - PID Set 2, Direct Dead BandPID Set 2 - Set the offset of the cool (direct) proportional band from set point in process units.,Config-
uration Multiple PID Sets 1,,0 to 999000,0,701-702 (R/W) (/1000)
Loop 1 - PID Set 2 Crossover PointSet crossover value to switch from PID Set 2 to PID Set 3.,Configuration Loop Settings 1,,-30000000 to
30000000,30000000,671-672 (R/W) (/1000)
Parameter Name
and Description
Web Page
Your
Settings
Range
Default
Modbus*
(Read/write and
scaling)
Loop 1 - PID Set 2 Indirect
Integral
Set the heat (indirect) integral
in minutes per repeat.
Configuration Multiple
PID Sets 1
0 to 99990 minutes
0
697-698 (R/W)
(/1000)
Loop 1 - PID Set 2 Indirect
Derivative
Set the heat (indirect) deriva-
tive time in minutes.
Configuration Multiple
PID Sets 1
0 to 9990 minutes
0
699-700 (R/W)
(/1000)
Loop 1 - PID Set 2 Indirect
Dead Band
Set the offset of the heat (indi-
rect) proportional band from set
point in process units.
Configuration Multiple
PID Sets 1
0 to 999000 degrees or units 0
693-694 (R/W)
(/1000)
Loop 1 - PID Set 2 Direct
Prop Band
Set the cool (direct) proportional
band from set point in process
units.
Configuration Multiple
PID Sets 1
1000 to 999000 degrees or
units
25000
703-704 (R/W)
(/1000)
Loop 1 - PID Set 2 Direct
Integral
Set the cool (direct) integral in
minutes per repeat.
Configuration Multiple
PID Sets 1
0 to 99990 minutes
0
705-706 (R/W)
(/1000)
Loop 1 - PID Set 2 Direct
Derivative
Set the cool (direct) derivative
time in minutes.
Configuration Multiple
PID Sets 1
0 to 9990 minutes
0
707-708 (R/W)
(/1000)
Loop 1 - PID Set 2 Direct
Dead Band
Set the offset of the cool (di-
rect) proportional band from
set point in process units.
Configuration Multiple
PID Sets 1
0 to 999000 degrees or units 0
701-702 (R/W)
(/1000)
Loop 1 - PID Set 2 Crossover
Point
Set crossover value to switch
from PID Set 2 to PID Set 3.
Configuration Loop
Settings 1
-30000000 to 30000000
degrees or units
30000000
671-672 (R/W)
(/1000)