Watlow Series PD User Manual

Page 89

background image

W a t l o w S e r i e s P D

87

C h a p t e r 9 D e v i c e C o n f i g T a b l e

Device Configuration > Control Loops > Loop 2 > PID Set 3

Loop 2 - PID Set 3, Indirect Prop BandPID Set 3 - Set the heat (indirect) proportional band from set point in process units.,Configuration
Multiple PID Sets 2,,1000 to 999000,25000,831-832 (R/W) (/1000)
Loop 2 - PID Set 3, Indirect IntegralPID Set 3 - Set the heat (indirect) integral in minutes per repeat.,Configuration Multiple PID Sets 2,,0
to 99990,0,833-834 (R/W) (/1000)
Loop 2 - PID Set 3, Indirect DerivativePID Set 3 - Set the heat (indirect) derivative time in minutes.,Configuration Multiple PID Sets 2,,0 to
9990,0,835-836 (R/W) (/1000)
Loop 2 - PID Set 3, Indirect Dead BandPID Set 3 - Set the offset of the heat (indirect) proportional band from set point in process
units.,Configuration Multiple PID Sets 2,,0 to 999000,0,829-830 (R/W) (/1000)
Loop 2 - PID Set 3, Direct Prop BandPID Set 3 - Set the cool (direct) proportional band from set point in process units.,Configuration Multi-
ple PID Sets 2,,1000 to 999000,25000,839-840 (R/W) (/1000)
Loop 2 - PID Set 3, Direct IntegralPID Set 3 - Set the cool (direct) integral in minutes per repeat.,Configuration Multiple PID Sets 2,,0 to
99990,0,841-842 (R/W) (/1000)
Loop 2 - PID Set 3, Direct DerivativePID Set 3 - Set the cool (direct) derivative time in minutes.,Configuration Multiple PID Sets 2,,0 to
9990,0,843-844 (R/W) (/1000)
Loop 2 - PID Set 3, Direct Dead BandPID Set 3 - Set the offset of the cool (direct) proportional band from set point in process units.,Config-
uration Multiple PID Sets 2,,0 to 999000,0,837-838 (R/W) (/1000)
Loop 2 - PID Set 3 Crossover PointSet crossover value to switch from PID Set 3 to PID Set 4.,Configuration Loop Settings 2,,-30000000 to
30000000,30000000,793-794 (R/W) (/1000)

Parameter Name

and Description

Web Page

Your

Settings

Range

Default

Modbus*

(Read/write and

scaling)

Loop 2 - PID Set 3 Indirect
Prop Band

Set the heat (indirect) propor-
tional band from set point in
process units.

Configuration Multiple
PID Sets 2

1000 to 999000 degrees or
units

25000

831-832 (R/W)
(/1000)

Loop 2 - PID Set 3 Indirect
Integral

Set the heat (indirect) integral
in minutes per repeat.

Configuration Multiple
PID Sets 2

0 to 99990 minutes

0

833-834 (R/W)
(/1000)

Loop 2 - PID Set 3 Indirect
Derivative

Set the heat (indirect) deriva-
tive time in minutes.

Configuration Multiple
PID Sets 2

0 to 9990 minutes

0

835-836 (R/W)
(/1000)

Loop 2 - PID Set 3 Indirect
Dead Band

Set the offset of the heat (indi-
rect) proportional band from
set point in process units.

Configuration Multiple
PID Sets 2

0 to 999000 degrees or units 0

829-830 (R/W)
(/1000)

Loop 2 - PID Set 3 Direct
Prop Band

Set the cool (direct) propor-
tional band from set point in
process units.

Configuration Multiple
PID Sets 2

1000 to 999000 degrees or
units

25000

839-840 (R/W)
(/1000)

Loop 2 - PID Set 3 Direct
Integral

Set the cool (direct) integral in
minutes per repeat.

Configuration Multiple
PID Sets 2

0 to 99990 minutes

0

841-842 (R/W)
(/1000)

Loop 2 - PID Set 3 Direct
Derivative

Set the cool (direct) derivative
time in minutes.

Configuration Multiple
PID Sets 2

0 to 9990 minutes

0

843-844 (R/W)
(/1000)

Loop 2 - PID Set 3 Direct
Dead Band

Set the offset of the cool (di-
rect) proportional band from
set point in process units.

Configuration Multiple
PID Sets 2

0 to 999000 degrees or units 0

837-838 (R/W)
(/1000)

Loop 2 - PID Set 3 Crossover
Point

Set crossover value to switch
from PID Set 3 to PID Set 4.

Configuration Loop
Settings 2

-30000000 to 30000000
degrees or units

30000000

793-794 (R/W)
(/1000)