Watlow Series PD User Manual
Page 87
W a t l o w S e r i e s P D
■
85
■
C h a p t e r 9 D e v i c e C o n f i g T a b l e
Device Configuration > Control Loops > Loop 2 > PID Set 1
Loop 2 - PID Crossover SourceSpecify to switch PID sets based on a set point or a process value.,Configuration Loop Settings 2,,Process Val-
ue (0)Set Point (1),Process Value (0),788 (R/W)
Loop 2 - PID Set 1, Indirect Prop BandPID Set 1 - Set the heat (indirect) proportional band from set point in process units.,Configuration
Loop Settings 2Configuration Multiple PID Sets 2,,1000 to 999000,25000,799-800 (R/W) (/1000)
Loop 2 - PID Set 1, Indirect IntegralPID Set
1 - Set the heat (indirect) integral in minutes per repeat.,Configuration Loop Settings 2Configuration Multiple PID Sets 2,,0 to 99990,0,8
01-802 (R/W) (/1000)
Loop 2 - PID Set 1, Indirect DerivativePID Set 1 - Set the heat (indirect) derivative time in minutes.,Configuration Loop Settings 2Configu-
ration Multiple PID Sets 2,,0 to 9990,0,803-804 (R/W) (/1000)
Loop 2 - PID Set 1, Indirect Dead BandPID Set 1 - Set the offset of the heat (indirect) proportional band from set point in process
units.,Configuration Loop Settings 2Configuration Multiple PID Sets 2,,0 to 999000,0,797-798 (R/W) (/1000)
Loop 2 - PID Set 1, Direct Prop BandPID Set 1 - Set the cool (direct) proportional band from set point in process units.,Configuration Loop
Settings 2Configuration Multiple PID Sets 2,,1000 to 999000,25000,807-808 (R/W) (/1000)
Loop 2 - PID Set 1, Direct IntegralPID Set 1 - Set the cool (direct) integral in minutes per repeat.,Configuration Loop Settings 2Configura-
tion Multiple PID Sets 2,,0 to 99990,0,809-810 (R/W) (/1000)
Loop 2 - PID Set 1, Direct DerivativePID Set 1 - Set the cool (direct) derivative time in minutes.,Configuration Loop Settings 2Configura-
tion Multiple PID Sets 2,,0 to 9990,0,811-812 (R/W) (/1000)
Loop 2 - PID Set 1, Direct Dead BandPID Set 1 - Set the offset of the cool (direct) proportional band from set point in process units.,Config-
uration Loop Settings 2Configuration Multiple PID Sets 2,,0 to 999000,0,805-806 (R/W) (/1000)
Loop 2 - PID Set 1 Crossover PointSet crossover value to switch from PID Set 1 to PID Set 2.,Configuration Loop Settings 2,,-30000000 to
30000000,30000000,789-790 (R/W) (/1000)
Parameter Name
and Description
Web Page
Your
Settings
Range
Default
Modbus*
(Read/write and
scaling)
Loop 2 - PID Crossover Source
Specify to switch PID sets
based on a set point or a
process value.
Configuration Loop
Settings 2
Process Value (0)
Set Point (1)
Process Value
(0)
788 (R/W)
Loop 2 - PID Set 1 Indirect
Prop Band
Set the heat (indirect) propor-
tional band from set point in
process units.
Configuration Loop
Settings 2
Configuration Multiple
PID Sets 2
1000 to 999000 degrees or
units
25000
799-800 (R/W)
(/1000)
Loop 2 - PID Set 1 Indirect
Integral
Set the heat (indirect) integral
in minutes per repeat.
Configuration Loop
Settings 2
Configuration Multiple
PID Sets 2
0 to 99990 minutes
0
801-802 (R/W)
(/1000)
Loop 2 - PID Set 1 Indirect
Derivative
Set the heat (indirect) derivative
time in minutes.
Configuration Loop
Settings 2
Configuration Multiple
PID Sets 2
0 to 9990 minutes
0
803-804 (R/W)
(/1000)
Loop 2 - PID Set 1 Indirect
Dead Band
Set the offset of the heat (indi-
rect) proportional band from set
point in process units.
Configuration Loop
Settings 2
Configuration Multiple
PID Sets 2
0 to 999000 degrees or units 0
797-798 (R/W)
(/1000)
Loop 2 - PID Set 1 Direct
Prop Band
Set the cool (direct) proportional
band from set point in process
units.
Configuration Loop
Settings 2
Configuration Multiple
PID Sets 2
1000 to 999000 degrees or
units
25000
807-808 (R/W)
(/1000)
Loop 2 - PID Set 1 Direct
Integral
Set the cool (direct) integral in
minutes per repeat.
Configuration Loop
Settings 2
Configuration Multiple
PID Sets 2
0 to 99990 minutes
0
809-810 (R/W)
(/1000)
Loop 2 - PID Set 1 Direct
Derivative
Set the cool (direct) derivative
time in minutes.
Configuration Loop
Settings 2
Configuration Multiple
PID Sets 2
0 to 9990 minutes
0
811-812 (R/W)
(/1000)
Loop 2 - PID Set 1 Direct
Dead Band
Set the offset of the cool (direct)
proportional band from set point
in process units.
Configuration Loop
Settings 2
Configuration Multiple
PID Sets 2
0 to 999000 degrees or units 0
805-806 (R/W)
(/1000)
Loop 2 - PID Set 1 Crossover
Point
Set crossover value to switch
from PID Set 1 to PID Set 2.
Configuration Loop
Settings 2
-30000000 to 30000000
degrees or units
30000000
789-790 (R/W)
(/1000)