Watlow Series PD User Manual

Page 88

background image

W a t l o w S e r i e s P D

86

C h a p t e r 9 D e v i c e C o n f i g T a b l e

Device Configuration > Control Loops > Loop 2 > PID Set 2

Loop 2 - PID Set 2, Indirect Prop BandPID Set 2 - Set the heat (indirect) proportional band from set point in process units.,Configuration
Multiple PID Sets 2,,1000 to 999000,25000,815-816 (R/W) (/1000)
Loop 2 - PID Set 2, Indirect IntegralPID Set 2 - Set the heat (indirect) integral in minutes per repeat.,Configuration Multiple PID Sets 2,,0
to 99990,0,817-818 (R/W) (/1000)
Loop 2 - PID Set 2, Indirect DerivativePID Set 2 - Set the heat (indirect) derivative time in minutes.,Configuration Multiple PID Sets 2,,0 to
9990,0,819-820 (R/W) (/1000)
Loop 2 - PID Set 2, Indirect Dead BandPID Set 2 - Set the offset of the heat (indirect) proportional band from set point in process
units.,Configuration Multiple PID Sets 2,,0 to 999000,0,813-814 (R/W) (/1000)
Loop 2 - PID Set 2, Direct Prop BandPID Set 2 - Set the cool (direct) proportional band from set point in process units.,Configuration Multi-
ple PID Sets 2,,1000 to 999000,25000,823-824 (R/W) (/1000)
Loop 2 - PID Set 2, Direct IntegralPID Set 2 - Set the cool (direct) integral in minutes per repeat.,Configuration Multiple PID Sets 2,,0 to
99990,0,825-826 (R/W) (/1000)
Loop 2 - PID Set 2, Direct DerivativePID Set 2 - Set the cool (direct) derivative time in minutes.,Configuration Multiple PID Sets 2,,0 to
9990,0,827-828 (R/W) (/1000)
Loop 2 - PID Set 2, Direct Dead BandPID Set 2 - Set the offset of the cool (direct) proportional band from set point in process units.,Config-
uration Multiple PID Sets 2,,0 to 999000,0,821-822 (R/W) (/1000)
Loop 2 - PID Set 2 Crossover PointSet crossover value to switch from PID Set 2 to PID Set 3.,Configuration Loop Settings 2,,-30000000 to
30000000,30000000,791-792 (R/W) (/1000)

Parameter Name

and Description

Web Page

Your

Settings

Range

Default

Modbus*

(Read/write and

scaling)

Loop 2 - PID Set 2 Indirect
Prop Band

Set the heat (indirect) propor-
tional band from set point in
process units.

Configuration Multiple
PID Sets 2

1000 to 999000 degrees or
units

25000

815-816 (R/W)
(/1000)

Loop 2 - PID Set 2 Indirect
Integral

Set the heat (indirect) integral
in minutes per repeat.

Configuration Multiple
PID Sets 2

0 to 99990 minutes

0

817-818 (R/W)
(/1000)

Loop 2 - PID Set 2 Indirect
Derivative

Set the heat (indirect) deriva-
tive time in minutes.

Configuration Multiple
PID Sets 2

0 to 9990 minutes

0

819-820 (R/W)
(/1000)

Loop 2 - PID Set 2 Indirect
Dead Band
Set the offset of the heat (indirect)
proportional band from set point
in process units.

Configuration Multiple
PID Sets 2

0 to 999000 degrees or units 0

813-814 (R/W)
(/1000)

Loop 2 - PID Set 2 Direct
Prop Band

Set the cool (direct) propor-
tional band from set point in
process units.

Configuration Multiple
PID Sets 2

1000 to 999000 degrees or
units

25000

823-824 (R/W)
(/1000)

Loop 2 - PID Set 2 Direct
Integral

Set the cool (direct) integral in
minutes per repeat.

Configuration Multiple
PID Sets 2

0 to 99990 minutes

0

825-826 (R/W)
(/1000)

Loop 2 - PID Set 2 Direct
Derivative

Set the cool (direct) derivative
time in minutes.

Configuration Multiple
PID Sets 2

0 to 9990 minutes

0

827-828 (R/W)
(/1000)

Loop 2 - PID Set 2 Direct
Dead Band

Set the offset of the cool (di-
rect) proportional band from
set point in process units.

Configuration Multiple
PID Sets 2

0 to 999000 degrees or units 0

821-822 (R/W)
(/1000)

Loop 2 - PID Set 2 Crossover
Point

Set crossover value to switch
from PID Set 2 to PID Set 3.

Configuration Loop
Settings 2

-30000000 to 30000000
degrees or units

30000000

791-792 (R/W)
(/1000)