C h a p t e r 9 D e v i c e C o n f i g T a b l e
Parameter Name
and Description
Web Page
Your
Settings
Range
Default
Modbus*
(Read/write and
scaling)
Analog Input 1 - Filter MethodSet the filter method. This smoothes out a rapidly changing input signal.,Configuration Analog Input 1,,Off
(0)First Order (1),Off (0),268 (R/W)
Analog Input 1 - Filter Time BaseSet the filter time for input in seconds.,Configuration Analog Input 1,,100 to 60000,100,269-270 (R/W)
(/1000)
Analog Input 1 - Single Offset ValueSet calibration single set point offset value. This allows compensation for lead resistance and sensor
error.,Configuration Analog Input 1,,-9999000 to 9999000,0,266-267 (R/W) (/1000)
Analog Input 1 - Failure Latching AcknowledgeAllows latched inputs errors to be acknowleded and cleared if sensor is repaired.,Monitor
Analog Input 1 - Filter Method
Set the filter method. This
smoothes out a rapidly changing
input signal.
Configuration Analog
Input 1
Off (0)
First Order (1)
Off (0)
268 (R/W)
Analog Input 1 - Filter Time
Base
Set the filter time for input in
seconds.
Configuration Analog
Input 1
100 to 60000 seconds
100
269-270 (R/W)
(/1000)
Analog Input 1 - Single Offset
Value
Set calibration single set point
offset value. This allows com-
pensation for lead resistance
and sensor error.
Configuration Analog
Input 1
-9999000 to 9999000
degrees or units
0
266-267 (R/W)
(/1000)
Analog Input 1 - Failure
Latching Acknowledge
Allows latched inputs errors
to be acknowleded and cleared
if sensor is repaired.
Monitor Device
Trend Information
No (0)
Yes (1)
Yes (1)
38 (R/W)