Watlow Series PD User Manual
Page 72
W a t l o w S e r i e s P D
■
70
■
C h a p t e r 9 D e v i c e C o n f i g T a b l e
Parameter Name
and Description
Web Page
Your
Settings
Range
Default
Modbus*
(Read/write and
scaling)
CT Input 4 - Sensor TypeSet the analog sensor type.,Configuration CT Input 4,,None (0)CT Current (6),None (0),331 (R/W)
CT Input 4 - CT PrecisionSet the decimal place for the input value when utilizing process type input that will be displayed in the browser
only.,Configuration CT Input 4,,0 (0)0 (1)0 (2)0 (3),0 (0),1128 (R)
CT Input 4 - CT UnitsSet the units for CT Input 4 that will be displayed in the browser only.,Configuration CT Input 4,,,,1129-1130 (R)
CT Input 4 - Low CT ScaleSet unit value for low CT scale.This setting is the displayed CT value when the analog input is at
minimum.,Configuration CT Input 4,,-30000000 to 30000000,-30000000,336-337 (R/W) (/1000)
CT Input 4 - High CT ScaleSet unit value for high CT scale. This setting is the displayed CT value when the analog input is at maxi-
mum.,Configuration CT Input 4,,-30000000 to 30000000,30000000,338-339 (R/W) (/1000)
CT Input 4 - Low Current ScaleSet unit value for low end of current range. This setting determines range of input.,Configuration CT In-
put 4,,0 to 50000,0,332-333 (R/W) (/1000)
CT Input 4 - High Current ScaleSet unit value for high end of current range. This setting determines range of input.,Configuration CT In-
put 4,,0 to 50000,20000,334-335 (R/W) (/1000)
CT Input 4 - Output SourceSelect output CT source to monitor.,Configuration CT Input 4,,Output 1 (0)Output 2 (1)Output 3 (2)Output 4
(3),Output 2 (1),342 (R/W)
CT Input 4 - Single Offset ValueSet calibration single set point offset value.This allows compensation for lead resistance and sensor er-
ror.,Configuration CT Input 4,,-9999000 to 9999000,0,340-341 (R/W) (/1000)
CT Input 4 - Sensor Type
Set the analog sensor type.
Configuration CT
Input 4
None (0)
CT Current (6)
None (0)
331 (R/W)
CT Input 4 - CT Precision
Set the decimal place for the
input value when utilizing
process type input that will be
displayed in the browser only.
Configuration CT
Input 4
0 (0)
0.0 (1)
0.00 (2)
0.000 (3)
0 (0)
1128 (R)
CT Input 4 - CT Units
Set the units for CT Input 4
that will be displayed in the
browser only.
Configuration CT
Input 4
Up to four alpha-numeric
characters.
1129-1130 (R)
CT Input 4 - Low CT Scale
Set unit value for low CT
scale.This setting is the
displayed CT value when the
analog input is at minimum.
Configuration CT
Input 4
-30000000 to 30000000
units
-30000000
336-337 (R/W)
(/1000)
CT Input 4 - High CT Scale
Set unit value for high CT
scale. This setting is the
displayed CT value when the
analog input is at maximum.
Configuration CT
Input 4
-30000000 to 30000000
units
30000000
338-339 (R/W)
(/1000)
CT Input 4 - Low Current
Scale
Set unit value for low end of
current range. This setting
determines range of input.
Configuration CT
Input 4
0 to 50000 units
0
332-333 (R/W)
(/1000)
CT Input 4 - High Current
Scale
Set unit value for high end of
current range. This setting
determines range of input.
Configuration CT
Input 4
0 to 50000 units
20000
334-335 (R/W)
(/1000)
CT Input 4 - Output Source
Select output CT source to
monitor.
Configuration CT
Input 4
Output 1 (0)
Output 2 (1)
Output 3 (2)
Output 4 (3)
Output 2 (1)
342 (R/W)
CT Input 4 - Single Offset Val-
ue
Set calibration single set point
offset value.This allows com-
pensation for lead resistance
and sensor error.
Configuration CT
Input 4
-9999000 to 9999000 units
0
340-341 (R/W)
(/1000)