Page 183

background image

Name and Description

Web Page

Range (Scaling)

Iterations

Default

EIP Decimal (Hex)

Modbus

EIP Data Type

Access

Silencing
Select whether to allow the operator to disable the
alarm output before the process value returns to
normal.

Alarm {1 to 8}

Configuration

No (0)

Yes (1)

Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Alarm 7
Alarm 8

No (0)

105/1/6 (69/1/6)
105/2/6 (69/2/6)
105/3/6 (69/3/6)
105/4/6 (69/4/6)
105/5/6 (69/5/6)
105/6/6 (69/6/6)
105/7/6 (69/7/6)
105/8/6 (69/8/6)

537
551
565
579
593
607
621
635

UINT

R/W

Blocking
Select to block this alarm until the process value
enters the normal range after turning the power on
or after a set point change.

Alarm {1 to 8}

Configuration

Off (0)

Set Point Change (1)

Power On (2)

Set Point Change and

Power On (3)

Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Alarm 7
Alarm 8

Off (0)

105/1/5 (69/1/5)
105/2/5 (69/2/5)
105/3/5 (69/3/5)
105/4/5 (69/4/5)
105/5/5 (69/5/5)
105/6/5 (69/6/5)
105/7/5 (69/7/5)
105/8/5 (69/8/5)

536
550
564
578
592
606
620
634

UINT

R/W

Device Configuration > Network > Email
SMTP Server IP Resolution
Specify the method to determine the SMTP server.

Device Configuration

Network

Email

Server Name (0)

Fixed Address (1)

Server Name (0)

Web page only

Web page only

R/W

SMTP Server Name
Specify the SMTP server name.

Device Configuration

Network

Email

0

Web page only

Web page only

R/W

SMTP Server Fixed Address
Specify the SMTP server's fixed IP address.

Device Configuration

Network

Email

-2,147,483,647 to

2,147,483,647

-1,062,731,775

Web page only

Web page only

R/W

Source Email Address
Specify the return source of submitted email. This
source is included in sent emails.

Device Configuration

Network

Email

0

Web page only

Web page only

R/W

Email Recipient {1 to 4}
Specify an email recipient. Up to four mail boxes
may receive an email.

Device Configuration

Network

Email

0

Web page only

Web page only

R/W

Device Configuration > Data Logging > Settings
Data Logging
Enable or disable data logging.

Datalog Configuration

No (0)

Yes (1)

No (0)

107/1/20 (6B/1/14)

1209

UINT

R/W

Parameters to Data Log: Process Value {1 to 4}
Specify whether to include the corresponding
process value in the datalog.

Datalog Configuration

No (0)

Yes (1)

Process Value 1
Process Value 2
Process Value 3
Process Value 4

No (0)

107/1/2 (6B/1/2)
107/1/3 (6B/1/3)
107/1/4 (6B/1/4)
107/1/5 (6B/1/5)

1191
1192
1193
1194

UINT

R/W

Parameters to Data Log: Working Set Point {1
or 2}
Specify to whether to include the corresponding
set point in the datalog.

Datalog Configuration

No (0)

Yes (1)

Set Point 1
Set Point 2

No (0)

107/1/6 (6B/1/6)
107/1/6 (6B/1/6)

1195
1196

UINT

R/W

Parameters to Data Log: Loop Power {1 or 2}
Specify whether to include the corresponding
power output in the datalog.

Datalog Configuration

No (0)

Yes (1)

Loop 1
Loop 2

No (0)

107/1/10 (6B/1/A)
107/1/11 (6B/1/B)

1199
1200

UINT

R/W

Parameters to Data Log: {Digital or CT} Input
{3 or 4} Status
Specify whether to include the corresponding
digital input status in the datalog.

Datalog Configuration

No (0)

Yes (1)

Digital or CT

Input 3

Digital or CT

Input 4

No (0)

107/1/8 (6B/1/8)
107/1/9 (6B/1/9)

1197
1198

UINT

R/W

SERIES PD with EtherNet/IP

Addressing Information (rev c) 181