Watlow Series PD User Manual
Page 171
Name and Description
Web Page
Range (Scaling)
Iterations
Default
EIP Decimal (Hex)
Modbus
EIP Data Type
Access
Monitor Device
Analog Input {1 or 2} - Active Process Value
Indicates the process value displayed on web page
and used by the control loop.
Monitor Device
-30,000,000 to 30,000,000
(/1000)
Analog Input 1
Analog Input 2
101/1/3 (65/1/3)
101/1/8 (65/1/8)
35-36
47-48
DINT
R
Digital Input {3 or 4} Value
Indicates the state of the digital input.
Monitor Device
Inactive (0)
Active (1)
Digital Input 3
Digital Input 4
Inactive (0)
101/1/21 (65/1/15)
101/1/26 (65/1/1A)
61
68
UINT
R
CT Input {3 or 4} - Active Process Value
Indicates the process value displayed on web page
and used by the control loop.
Monitor Device
-30,000,000 to 30,000,000
(/1000)
CT Input 3
CT Input 4
101/1/13 (65/1/D)
101/1/18 (65/1/12)
53-54
57-58
DINT
R
Analog Input {1 to 4} - Error Status
Display active errors for the analog input.
Monitor Device
No Fault (0)
Ambient Fault (1)
Under Range Fault (2)
Over Range Fault (3)
Under Flow Fault (4)
Over Flow Fault (5)
INFOSENSE Fault (6)
Lead Compensation Fault
(7)
Analog Input 1
Analog Input 2
Analog Input 3
Analog Input 4
101/1/4 (65/1/4)
101/1/9 (65/1/9)
101/1/14 (65/1/E)
101/1/19 (65/1/13)
37
49
55
59
UINT
R
Failure Latching Acknowledge
Resets latched input errors if sensor is repaired.
Monitor Device
No (0)
Yes (1)
Loop 1
Loop 2
Yes (1)
101/1/5 (65/1/5)
101/1/10 (65/1/A)
38
50
UINT
R/W
Digital Input 3 - Switch To Digital Set Point
Status
Indicates whether Digital Input 3 has switched the
loop to the digital setpoint.
Monitor Device
Inactive (0)
Active (1)
Loop 1
Loop 2
Inactive (0)
101/1/24 (65/1/18)
101/1/29 (65/1/1D)
64
71
UINT
R
Digital Input 4 - Switch To Digital Set Point
Status
Indicates whether Digital Input 4 has switched the
loop to the digital setpoint.
Monitor Device
Inactive (0)
Active (1)
Loop 1
Loop 2
Inactive (0)
101/1/25 (65/1/19)
101/1/30 (65/1/1E)
65
72
UINT
R
Digital Input Switch Loop {1 or 2} Off Status
Indicates whether a digital input has switched the
loop off.
Monitor Device
Inactive (0)
Active (1)
Loop 1
Loop 2
Inactive (0)
101/1/23 (65/1/17)
101/1/28 (65/1/1C)
63
70
UINT
R
Digital Input Switch Loop {1 or 2} to Manual
Status
Indicates whether a digital input has switched the
loop to manual.
Monitor Device
Inactive (0)
Active (1)
Loop 1
Loop 2
Inactive (0)
101/1/22 (65/1/16)
101/1/27 (65/1/1B)
62
69
UINT
R
Working Set Point
Indicates the active set point, whether the auto set
point, digital set point or the ramp to set point.
Monitor Device
(/1000)
Loop 1
Loop 2
75000
101/1/33 (65/1/21)
101/1/41 (65/1/29)
78-79
92-93
DINT
R
Loop Power (Indirect)
Indicates the heat (indirect) output power
Monitor Device
0 to 10,000 (/100)
Loop 1
Loop 2
101/1/37 (65/1/25)
101/1/45 (65/1/2D)
83
97
INT
R
Loop Power (Direct)
Indicates the cool (direct) output power.
Monitor Device
0 to 10,000 (/100)
Loop 1
Loop 2
101/1/38 (65/1/26)
101/1/46 (65/1/2E)
84
98
INT
R
Auto Set Point
Set the closed loop (auto) setpoint for control loop.
Monitor Device
(/1000)
Loop 1
Loop 2
75000
101/1/32 (65/1/20)
101/1/40 (65/1/28)
76-77
90-91
DINT
R/W
Manual Set Point
Set the a fixed output level, in percent power, in
manual mode.
Monitor Device
-10,000 to 10,000 (/100)
Loop 1
Loop 2
0
101/1/31 (65/1/1F)
101/1/39 (65/1/27)
75
89
INT
R/W
Mode
Choose open loop (manual) or closed loop (auto)
control.
Monitor Device
Off (0)
Manual (1)
Auto (2)
Loop 1
Loop 2
Off (0)
101/1/34 (65/1/22)
101/1/42 (65/1/2A)
80
94
UINT
R/W
Tuning Status/Control Loop Status
Monitor Device
No (0)
Yes (1)
Loop 1
Loop 2
No (0)
101/1/35 (65/1/23)
101/1/43 (65/1/2B)
81
95
UINT
R/W
SERIES PD with EtherNet/IP
Addressing Information (rev c)
169