Name and Description
Web Page
Range (Scaling)
Iterations
Default
EIP Decimal (Hex)
Modbus
EIP Data Type
Access
Cross Over Point 3
Set value to switch from PID set 3 to PID set 4.
Multiple PID Loop {1 or
2} Configuration
-30,000,000 to 30,000,000
(/1000)
Loop 1
Loop 2
30,000,000
106/1/16 (6A/1/10)
106/2/16 (6A/2/10)
673-674
793-794
DINT
R/W
Cross Over Point 4
Set value to switch from PID set 4 to PID set 5.
Multiple PID Loop {1 or
2} Configuration
-30,000,000 to 30,000,000
(/1000)
Loop 1
Loop 2
30,000,000
106/1/17 (6A/1/11)
106/2/17 (6A/2/11)
675-675
795-796
DINT
R/W
Device Configuration > Outputs > Output {1 to 4}
Output Function
Select the function of the output.
Output {1 to 4}
Configuration
Off (0)
Control (1)
Event (2)
Retransmit (3) (Outputs 1
and 3 only)
Output 1
Output 2
Output 3
Output 4
Off (0)
104/1/1 (68/1/1)
104/2/1 (68/2/1)
104/3/1 (68/3/1)
104/4/1 (68/4/1)
391
431
461
501
UINT
R/W
Output Direction
Select whether the output will perform heating
(indirect action) or cooling (direct action).
Output {1 to 4}
Configuration
Off (0)
Heat/Indirect (1)
Cool/Direct (2)
Output 1
Output 2
Output 3
Output 4
Off (0)
104/1/6 (68/1/6)
104/2/6 (68/2/6)
104/3/6 (68/3/6)
104/4/6 (68/4/6)
398
438
468
508
UINT
R/W
Control Source
Set which loop will control the output.
Output {1 to 4}
Configuration
Loop 1 (0)
Loop 2 (1)
Output 1
Output 2
Output 3
Output 4
Loop 1 (0)
104/1/3 (68/1/3)
104/2/3 (68/2/3)
104/3/3 (68/3/3)
104/4/3 (68/4/3)
393
433
463
503
UINT
R/W
Output Cycle Time
Set the cycle time in seconds.
Output {1 to 4}
Configuration
1 to 600 (/10)
0.1 to 60 seconds for non-
mechanical relay outputs
1.0 to 60 seconds for
mechanical relay outputs
Output 1
Output 2
Output 3
Output 4
1.0 second for non-
mechanical relay
outputs
10.0 seconds for
mechanical relay
outputs
104/1/2 (68/1/2)
104/2/2 (68/2/2)
104/3/2 (68/3/2)
104/4/2 (68/4/2)
392
432
462
502
INT
R/W
Output Mode Time Base
Select whether the output will operate with a fixed
or variable time-based control.
Output {1 to 4}
Configuration
Fixed (0)
Variable (1)
Output 1
Output 2
Output 3
Output 4
Fixed (0)
104/1/4 (68/1/4)
104/2/4 (68/2/4)
104/3/4 (68/3/4)
104/4/4 (68/4/4)
396
436
466
506
UINT
R/W
System Line Frequency
Specify the line frequency to use if zero cross line
frequency detection fails.
Output {1 to 4}
Configuration
50 Hz (0)
60 Hz (1)
60 Hz (1)
108/1/31 (6C/1/1F)
1075
UINT
R/W
Low Power Scale
Set the minimum percent value for the output.
Output {1 to 4}
Configuration
0 to 10,000 (/1000)
Output 1
Output 2
Output 3
Output 4
0
104/1/24 (68/1/18)
104/2/24 (68/2/18)
104/3/24 (68/3/18)
104/4/24 (68/4/18)
418-419
449-450
488-489
519-520
DINT
R/W
High Power Scale
Set the maximum percent value for the output.
Output {1 to 4}
Configuration
0 to 10,000 (/1000)
Output 1
Output 2
Output 3
Output 4
10,000
104/1/25 (68/1/19)
104/2/25 (68/2/19)
104/3/25 (68/3/19)
104/4/25 (68/4/19)
420-421
451-452
490-491
521-522
DINT
R/W
Analog Signal
Select analog output type.
Output {1 to 4}
Configuration
Voltage (0)
Current (1)
Output 1
Output 3
Voltage (0)
104/1/19 (68/1/13)
104/3/19 (68/3/13)
409
479
UINT
R/W
Low Voltage Scale
Set the voltage value that corresponds to the Low
Power Scale value.
Output {1 to 4}
Configuration
0 to 10,000 (/1000)
Output 1
Output 3
0
104/1/22 (68/1/16)
104/3/22 (68/3/16)
414-415
484-485
DINT
R/W
High Voltage Scale
Set the voltage value that corresponds to the High
Power Scale value.
Output {1 to 4}
Configuration
0 to 10,000 (/1000)
Output 1
Output 3
10,000
104/1/23 (68/1/17)
104/3/23 (68/3/17)
416-417
486-487
DINT
R/W
Low Current Scale
Set the current value that corresponds to the Low
Power Scale value.
Output {1 to 4}
Configuration
0 to 20,000 (/1000)
Output 1
Output 3
4,000
104/1/20 (68/1/14)
104/3/20 (68/3/14)
410-411
480-481
DINT
R/W
High Current Scale
Set the current value that corresponds to the High
Power Scale value.
Output {1 to 4}
Configuration
0 to 20,000 (/1000)
Output 1
Output 3
20,000
104/1/21 (68/1/15)
104/3/21 (68/3/15)
412-413
482-483
DINT
R/W
SERIES PD with EtherNet/IP
Addressing Information (rev c) 177