Name and Description

Web Page

Range (Scaling)

Iterations

Default

EIP Decimal (Hex)

Modbus

EIP Data Type

Access

Cross Over Point 3
Set value to switch from PID set 3 to PID set 4.

Multiple PID Loop {1 or

2} Configuration

-30,000,000 to 30,000,000

(/1000)

Loop 1
Loop 2

30,000,000

106/1/16 (6A/1/10)
106/2/16 (6A/2/10)

673-674
793-794

DINT

R/W

Cross Over Point 4
Set value to switch from PID set 4 to PID set 5.

Multiple PID Loop {1 or

2} Configuration

-30,000,000 to 30,000,000

(/1000)

Loop 1
Loop 2

30,000,000

106/1/17 (6A/1/11)
106/2/17 (6A/2/11)

675-675
795-796

DINT

R/W

Device Configuration > Outputs > Output {1 to 4}
Output Function
Select the function of the output.

Output {1 to 4}

Configuration

Off (0)

Control (1)

Event (2)

Retransmit (3) (Outputs 1

and 3 only)

Output 1
Output 2
Output 3
Output 4

Off (0)

104/1/1 (68/1/1)
104/2/1 (68/2/1)
104/3/1 (68/3/1)
104/4/1 (68/4/1)

391
431
461
501

UINT

R/W

Output Direction
Select whether the output will perform heating
(indirect action) or cooling (direct action).

Output {1 to 4}

Configuration

Off (0)

Heat/Indirect (1)

Cool/Direct (2)

Output 1
Output 2
Output 3
Output 4

Off (0)

104/1/6 (68/1/6)
104/2/6 (68/2/6)
104/3/6 (68/3/6)
104/4/6 (68/4/6)

398
438
468
508

UINT

R/W

Control Source
Set which loop will control the output.

Output {1 to 4}

Configuration

Loop 1 (0)
Loop 2 (1)

Output 1
Output 2
Output 3
Output 4

Loop 1 (0)

104/1/3 (68/1/3)
104/2/3 (68/2/3)
104/3/3 (68/3/3)
104/4/3 (68/4/3)

393
433
463
503

UINT

R/W

Output Cycle Time
Set the cycle time in seconds.

Output {1 to 4}

Configuration

1 to 600 (/10)

0.1 to 60 seconds for non-

mechanical relay outputs

1.0 to 60 seconds for

mechanical relay outputs

Output 1
Output 2
Output 3
Output 4

1.0 second for non-

mechanical relay

outputs

10.0 seconds for

mechanical relay

outputs

104/1/2 (68/1/2)
104/2/2 (68/2/2)
104/3/2 (68/3/2)
104/4/2 (68/4/2)

392
432
462
502

INT

R/W

Output Mode Time Base
Select whether the output will operate with a fixed
or variable time-based control.

Output {1 to 4}

Configuration

Fixed (0)

Variable (1)

Output 1
Output 2
Output 3
Output 4

Fixed (0)

104/1/4 (68/1/4)
104/2/4 (68/2/4)
104/3/4 (68/3/4)
104/4/4 (68/4/4)

396
436
466
506

UINT

R/W

System Line Frequency
Specify the line frequency to use if zero cross line
frequency detection fails.

Output {1 to 4}

Configuration

50 Hz (0)
60 Hz (1)

60 Hz (1)

108/1/31 (6C/1/1F)

1075

UINT

R/W

Low Power Scale
Set the minimum percent value for the output.

Output {1 to 4}

Configuration

0 to 10,000 (/1000)

Output 1
Output 2
Output 3
Output 4

0

104/1/24 (68/1/18)
104/2/24 (68/2/18)
104/3/24 (68/3/18)
104/4/24 (68/4/18)

418-419
449-450
488-489
519-520

DINT

R/W

High Power Scale
Set the maximum percent value for the output.

Output {1 to 4}

Configuration

0 to 10,000 (/1000)

Output 1
Output 2
Output 3
Output 4

10,000

104/1/25 (68/1/19)
104/2/25 (68/2/19)
104/3/25 (68/3/19)
104/4/25 (68/4/19)

420-421
451-452
490-491
521-522

DINT

R/W

Analog Signal
Select analog output type.

Output {1 to 4}

Configuration

Voltage (0)
Current (1)

Output 1
Output 3

Voltage (0)

104/1/19 (68/1/13)
104/3/19 (68/3/13)

409
479

UINT

R/W

Low Voltage Scale
Set the voltage value that corresponds to the Low
Power Scale value.

Output {1 to 4}

Configuration

0 to 10,000 (/1000)

Output 1
Output 3

0

104/1/22 (68/1/16)
104/3/22 (68/3/16)

414-415
484-485

DINT

R/W

High Voltage Scale
Set the voltage value that corresponds to the High
Power Scale value.

Output {1 to 4}

Configuration

0 to 10,000 (/1000)

Output 1
Output 3

10,000

104/1/23 (68/1/17)
104/3/23 (68/3/17)

416-417
486-487

DINT

R/W

Low Current Scale
Set the current value that corresponds to the Low
Power Scale value.

Output {1 to 4}

Configuration

0 to 20,000 (/1000)

Output 1
Output 3

4,000

104/1/20 (68/1/14)
104/3/20 (68/3/14)

410-411
480-481

DINT

R/W

High Current Scale
Set the current value that corresponds to the High
Power Scale value.

Output {1 to 4}

Configuration

0 to 20,000 (/1000)

Output 1
Output 3

20,000

104/1/21 (68/1/15)
104/3/21 (68/3/15)

412-413
482-483

DINT

R/W