Watlow Series PD User Manual
Page 177
![background image](/manuals/359292/177/background.png)
Name and Description
Web Page
Range (Scaling)
Iterations
Default
EIP Decimal (Hex)
Modbus
EIP Data Type
Access
Ramp Action
Select what event(s) trigger a ramp to set point.
Control Loop {1 or 2}
Configuration
Off (0)
Startup (1)
SP Change (2)
Startup and SP Change
(3)
Loop 1
Loop 2
Off (0)
106/1/58 (6A/1/3A)
106/2/58 (6A/2/3A)
757
877
UINT
R/W
Ramp Rate
Set the interval of degrees or units that the
ramping set point will change per minute or hour,
as determined by the Ramp Interval setting.
Control Loop {1 or 2}
Configuration
0 to 9,999,000 (/1000)
Loop 1
Loop 2
100,000
106/1/60 (6A/1/3C)
106/2/60 (6A/2/3C)
759-760
879-880
DINT
R/W
Ramp Interval
Select the time unit that applies to the Ramp Rate
parameter.
Control Loop {1 or 2}
Configuration
Minute (0)
Hour (1)
Loop 1
Loop 2
Minute (0)
106/1/59 (6A/1/3B)
106/2/59 (6A/2/3B)
758
878
UINT
R/W
Device Configuration > Control Loops > Loop {1 or 2} Multiple PID Sets
Cross Over Source
Specify whether to switch the PID sets based on
the set point or process value.
Multiple PID Loop {1 or
2} Configuration
Process Value (0)
Set Point (1)
Loop 1
Loop 2
Process Value (0)
106/1/13 (6A/1/D)
106/2/13 (6A/2/D)
668
788
UINT
R/W
Heat (Indirect) Propband
Set the heat (indirect) proportional band in process
units.
Multiple PID Loop {1 or
2} Configuration
1,000 to 999,000 (/1000)
Loop 1 Set 1
Loop 1 Set 2
Loop 1 Set 3
Loop 1 Set 4
Loop 1 Set 5
Loop 2 Set 1
Loop 2 Set 2
Loop 2 Set 3
Loop 2 Set 4
Loop 2 Set 5
25,000
106/1/19 (6A/1/13)
106/1/27 (6A/1/1B)
106/1/35 (6A/1/23)
106/1/43 (6A/1/2B)
106/1/51 (6A/1/33)
106/2/19 (6A/2/13)
106/2/27 (6A/2/1B)
106/2/35 (6A/2/23)
106/2/43 (6A/2/2B)
106/2/51 (6A/2/33)
679-680
695-696
711-712
727-728
743-744
799-800
815-816
831-832
847-848
863-864
DINT
R/W
Heat (Indirect) Integral
Set the heat (indirect) integral in minutes per
repeat.
Multiple PID Loop {1 or
2} Configuration
0 to 99,990 (/1000)
Loop 1 Set 1
Loop 1 Set 2
Loop 1 Set 3
Loop 1 Set 4
Loop 1 Set 5
Loop 2 Set 1
Loop 2 Set 2
Loop 2 Set 3
Loop 2 Set 4
Loop 2 Set 5
0
106/1/20 (6A/1/14)
106/1/28 (6A/1/1C)
106/1/36 (6A/1/24)
106/1/44 (6A/1/2C)
106/1/52 (6A/1/34)
106/2/20 (6A/2/14)
106/2/28 (6A/2/1C)
106/2/36 (6A/2/24)
106/2/44 (6A/2/2C)
106/2/52 (6A/2/34)
681-682
697-698
713-714
729-730
745-746
801-802
817-818
833-834
849-850
865-866
DINT
R/W
Heat (Indirect) Derivative
Set the heat (indirect) derivative time in minutes.
Multiple PID Loop {1 or
2} Configuration
0 to 9,990 (/1000)
Loop 1 Set 1
Loop 1 Set 2
Loop 1 Set 3
Loop 1 Set 4
Loop 1 Set 5
Loop 2 Set 1
Loop 2 Set 2
Loop 2 Set 3
Loop 2 Set 4
Loop 2 Set 5
0
106/1/21 (6A/1/15)
106/1/29 (6A/1/1D)
106/1/37 (6A/1/25)
106/1/45 (6A/1/2D)
106/1/53 (6A/1/35)
106/2/21 (6A/2/15)
106/2/29 (6A/2/1D)
106/2/37 (6A/2/25)
106/2/45 (6A/2/2D)
106/2/53 (6A/2/35)
683-684
699-700
715-716
731-732
747-748
803-804
819-820
835-836
851-852
867-868
DINT
R/W
SERIES PD with EtherNet/IP
Addressing Information (rev c) 175