Name and Description

Web Page

Range (Scaling)

Iterations

Default

EIP Decimal (Hex)

Modbus

EIP Data Type

Access

Alarm Status
Indicates the status of the Alarm.

Monitor Device

Inactive or Off (0)

Active (1)

Silenced (2)

Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Alarm 7
Alarm 8

Inactive or Off (0)

101/1/47 (65/1/2F)
101/1/53 (65/1/35)
101/1/59 (65/1/3B)
101/1/65 (65/1/41)
101/1/71 (65/1/47)

101/1/77 (65/1/4D)

101/1/83 (65/1/53)
101/1/89 (65/1/59)

103
116
129
142
155
168
181
194

UINT

R

Latching Action
Select to clear a latched alarm after the process
value returns to normal.

Monitor Device

No (0)

Yes (1)

Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Alarm 7
Alarm 8

No (0)

101/1/52 (65/1/34)

101/1/58 (65/1/3A)

101/1/64 (65/1/40)
101/1/70 (65/1/46)

101/1/76 (65/1/4C)

101/1/82 (65/1/52)
101/1/88 (65/1/58)

101/1/94 (65/1/5E)

111
124
137
150
163
176
189
202

UINT

R/W

Silence Action
Select to silence an alarm.

Monitor Device

No (0)

Yes (1)

Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Alarm 7
Alarm 8

No (0)

101/1/51 (65/1/33)
101/1/57 (65/1/39)
101/1/63 (65/1/3F)
101/1/69 (65/1/45)

101/1/75 (65/1/4B)

101/1/81 (65/1/51)
101/1/87 (65/1/57)

101/1/93 (65/1/5D)

110
123
136
149
162
175
188
201

UINT

R/W

Analog Input {1 or 2} - Filtered Process Value
Indicates the filtered process value measured by
the corresponding analog input.

Monitor Device

-30,000,000 to 30,000,000

(/1000)

Analog Input 1
Analog Input 2

101/1/2 (65/1/2)
101/1/7 (65/1/7)

33-34
45-46

DINT

R

Analog Input {1 or 2} - Process Value
Indicates the unfiltered process value measured by
the corresponding analog input.

Monitor Device

-30,000,000 to 30,000,000

(/1000)

Analog Input 1
Analog Input 2

101/1/1 (65/1/1)
101/1/6 (65/1/6)

31-32
43-44

DINT

R

CT Input {3 or 4} - Filtered Process Value
Indicates the filtered process value measured by
the corresponding analog input.

Monitor Device

CT Input 3
CT Input 4

Web page only

Web page only

CT Input {3 or 4} - Process Value
Indicates the unfiltered process value measured by
the corresponding analog input .

Monitor Device

CT Input 3
CT Input 4

Web page only

Web page only

Alarm Latching / Silence Action
Set the coresponding bit to clear a latched alarm.
Bits 1 through 8 correspond to alarms 1 to 8.

Monitor Device

-32,768 to 32,767

0

101/1/100 (65/1/64)

WORD

R/W

Alarm Status
Read the corresponding bit to determine the alarm
status. 0 = inactive, 1 = active. Bits 1 to 8
correspond to alarms 1 to 8.

Monitor Device

-32,768 to 32,767

0

101/1/98 (65/1/62)

WORD

R

Analog Input Failure Latching Acknowledge
Set the corresponding bit to acknowledge the input
error. 1 = acknowledge. Bit 1 corresponds to
analog input 1 and bit 2 corresponds to analog
input 2.

Monitor Device

-32,768 to 32,767

0

101/1/99 (65/1/63)

WORD

R/W

Control Power Output

Monitor Device

-10000 to 10000 (/100)

Loop 1
Loop 2

0

101/1/96 (65/1/60)

INT

R

SERIES PD with EtherNet/IP

Addressing Information (rev c) 170