Name and Description
Web Page
Range (Scaling)
Iterations
Default
EIP Decimal (Hex)
Modbus
EIP Data Type
Access
Alarm Status
Indicates the status of the Alarm.
Monitor Device
Inactive or Off (0)
Active (1)
Silenced (2)
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Alarm 7
Alarm 8
Inactive or Off (0)
101/1/47 (65/1/2F)
101/1/53 (65/1/35)
101/1/59 (65/1/3B)
101/1/65 (65/1/41)
101/1/71 (65/1/47)
101/1/77 (65/1/4D)
101/1/83 (65/1/53)
101/1/89 (65/1/59)
103
116
129
142
155
168
181
194
UINT
R
Latching Action
Select to clear a latched alarm after the process
value returns to normal.
Monitor Device
No (0)
Yes (1)
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Alarm 7
Alarm 8
No (0)
101/1/52 (65/1/34)
101/1/58 (65/1/3A)
101/1/64 (65/1/40)
101/1/70 (65/1/46)
101/1/76 (65/1/4C)
101/1/82 (65/1/52)
101/1/88 (65/1/58)
101/1/94 (65/1/5E)
111
124
137
150
163
176
189
202
UINT
R/W
Silence Action
Select to silence an alarm.
Monitor Device
No (0)
Yes (1)
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Alarm 7
Alarm 8
No (0)
101/1/51 (65/1/33)
101/1/57 (65/1/39)
101/1/63 (65/1/3F)
101/1/69 (65/1/45)
101/1/75 (65/1/4B)
101/1/81 (65/1/51)
101/1/87 (65/1/57)
101/1/93 (65/1/5D)
110
123
136
149
162
175
188
201
UINT
R/W
Analog Input {1 or 2} - Filtered Process Value
Indicates the filtered process value measured by
the corresponding analog input.
Monitor Device
-30,000,000 to 30,000,000
(/1000)
Analog Input 1
Analog Input 2
101/1/2 (65/1/2)
101/1/7 (65/1/7)
33-34
45-46
DINT
R
Analog Input {1 or 2} - Process Value
Indicates the unfiltered process value measured by
the corresponding analog input.
Monitor Device
-30,000,000 to 30,000,000
(/1000)
Analog Input 1
Analog Input 2
101/1/1 (65/1/1)
101/1/6 (65/1/6)
31-32
43-44
DINT
R
CT Input {3 or 4} - Filtered Process Value
Indicates the filtered process value measured by
the corresponding analog input.
Monitor Device
CT Input 3
CT Input 4
Web page only
Web page only
CT Input {3 or 4} - Process Value
Indicates the unfiltered process value measured by
the corresponding analog input .
Monitor Device
CT Input 3
CT Input 4
Web page only
Web page only
Alarm Latching / Silence Action
Set the coresponding bit to clear a latched alarm.
Bits 1 through 8 correspond to alarms 1 to 8.
Monitor Device
-32,768 to 32,767
0
101/1/100 (65/1/64)
WORD
R/W
Alarm Status
Read the corresponding bit to determine the alarm
status. 0 = inactive, 1 = active. Bits 1 to 8
correspond to alarms 1 to 8.
Monitor Device
-32,768 to 32,767
0
101/1/98 (65/1/62)
WORD
R
Analog Input Failure Latching Acknowledge
Set the corresponding bit to acknowledge the input
error. 1 = acknowledge. Bit 1 corresponds to
analog input 1 and bit 2 corresponds to analog
input 2.
Monitor Device
-32,768 to 32,767
0
101/1/99 (65/1/63)
WORD
R/W
Control Power Output
Monitor Device
-10000 to 10000 (/100)
Loop 1
Loop 2
0
101/1/96 (65/1/60)
INT
R
SERIES PD with EtherNet/IP
Addressing Information (rev c) 170