beautypg.com

Output 4 solid-state relay, Output 4 switched dc, Output 4 open collector – Watlow Series PD User Manual

Page 20: Figure 18a, Figure 18b, Figure 18c

background image

W a t l o w S e r i e s P D

18

C h a p t e r 2 I n s t a l l a n d W i r e

ç

Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.

Quencharc Note:
Switching pilot duty loads (relay
coils, solenoids, etc.) with the
mechanical relay or solid-state
relay output options requires use
of an R.C. suppressor.

Watlow carries the R.C. suppres-
sor Quencharc brand name,
which is a trademark of ITW
Paktron. Watlow Part No. 0804-
0147-0000.

Note: 24 VЕ

Е input power re-

quired to use single cycle,vari-
able time base output function.

Figure 18a —

Output 4 Solid-state Relay

PD_ _ - _ _ _ K - _ _ _ _

• Form A.contact

• 0.5 A, resistive

• 20 VA pilot duty, 120/240VÅ (ac), inductive

• 24 to 240VÅ (ac)

• See Quencharc note

• Minimum load current 10mA

• Maximum leakage current 100µA

• Not for use with direct current (dc)

• Output does not supply power

Figure 18b —

Output 4 Switched DC

PD_ _ - _ _ _ C - _ _ _ _

• Maximum supply current 30 mAÎ (dc)

• Supply voltage 24VÎ (dc)

• Not recommended for switching mechanical relays

• Output supplies power

Figure 18c —

Output 4 Open Collector

PD_ _ - _ _ _ C - _ _ _ _

• Maximum current sink 200 mAÎ (dc)

• Maximum supply voltage 42VÎ (dc)

• Output does not supply power

Internal Circuitry

dc-

COM.

dc+

42VÎ (dc) maximum

Open Collector

22

24

23

Load

-

+

Power

Supply

-

+

Class 2 power source
required for agency
compliance.

22 23 24

24 dc -

22 dc +
23 com

Internal Circuitry

dc-

dc+

24VÎ (dc)

Load

Switched DC

-

+

22

24

22 23 24

24 dc -

22 dc +

23 com

Internal Circuitry

COM.

N.O.

Solid-state Relay

23

24

Solid-state Switch

22 23 24

24 normally open

23 com