Analog Input 2 - Low Current ScaleSet unit value for low end of current range. This setting determines range of input.,Configuration Ana-
log Input 2,,0 to 20000,4000,284-285 (R/W) (/1000)
Analog Input 2 - High Current ScaleSet unit value for high end of current range. This setting determines range of input.,Configuration
Analog Input 2,,0 to 20000,20000,286-287 (R/W) (/1000)
Analog Input 2 - Temperature Process Value UnitsSet the temperature units for thermocouple and RTD type inputs that will be displayed
in the browser only.,Configuration Analog Input 2,,(degrees symbol) F (0)(degrees symbol) C (1),(degrees symbol) F (0),1120 (R)
Analog Input 2 - Temperature Process Value PrecisionSet the decimal place for the input value of temperature when utilizing themocouple
or RTD input that will be displayed in the browser only.,Configuration Analog Input 2,,0 (0)0 (1),0 (0),1118 (R)
Analog Input 2 - Filter MethodSet the filter method. This smoothes out a rapidly changing input signal.,Configuration Analog Input 2,,Off
(0)First Order (1),Off (0),298 (R/W)
Analog Input 2 - Filter Time BaseSet the filter time for input in seconds.,Configuration Analog Input 2,,100 to 60000,100,299-300 (R/W)
(/1000)
Analog Input 2 - Single Offset ValueSet calibration single set point offset value. This allows compensation for lead resistance and sensor
error.,Configuration Analog Input 2,,-9999000 to 9999000,0,296-297 (R/W) (/1000)
Loop 2 - Failure LatchingSelect to latch input failure. If a sensor fails, an error is generated. This selection will latch intermittent
error.,Configuration Loop Settings 2,,Off (0)On (1),Off (0),780 (R/W)
Analog Input 2 - Failure Latching AcknowledgeAllows latched inputs errors to be acknowleded and cleared if sensor is repaired.,Monitor
Device,,No (0)Yes (1),Yes (1),50 (R/W)
Loop 2 - Failure Fixed PowerSelect output power level to apply if sensor on input produces errors and transition to manual (open loop) oc-
curs.,Configuration Loop Settings 2,,-10000 to 10000,0,781 (R/W) (/100)

W a t l o w S e r i e s P D

68

C h a p t e r 9 D e v i c e C o n f i g T a b l e

Parameter Name

and Description

Web Page

Your

Settings

Range

Default

Modbus*

(Read/write and

scaling)

Analog Input 2 - Low Current
Scale

Set unit value for low end of
current range. This setting
determines range of input.

Configuration Analog
Input 2

0 to 20000 units

4000

284-285 (R/W)
(/1000)

Analog Input 2 - High Current
Scale

Set unit value for high end of
current range. This setting
determines range of input.

Configuration Analog
Input 2

0 to 20000 units

20000

286-287 (R/W)
(/1000)

Analog Input 2 - Temperature
Process Value Units

Set the temperature units for
thermocouple and RTD type
inputs that will be displayed
in the browser only.

Configuration Analog
Input 2

Fahrenheit (0)
Celsius (1)

Fahrenheit (0) 1120 (R)

Analog Input 2 - Temperature
Process Value Precision

Set the decimal place for the
input value of temperature
when utilizing themocouple or
RTD input that will be dis-
played in the browser only.

Configuration Analog
Input 2

0 (0)
0.0 (1)

0 (0)

1118 (R)

Analog Input 2 - Filter Method

Set the filter method. This
smoothes out a rapidly chang-
ing input signal.

Configuration Analog
Input 2

Off (0)
First Order (1)

Off (0)

298 (R/W)

Analog Input 2 - Filter Time
Base

Set the filter time for input in
seconds.

Configuration Analog
Input 2

100 to 60000 seconds

100

299-300 (R/W)
(/1000)

Analog Input 2 - Single Offset
Value

Set calibration single set point
offset value. This allows com-
pensation for lead resistance
and sensor error.

Configuration Analog
Input 2

-9999000 to 9999000
degrees or units

0

296-297 (R/W)
(/1000)

Loop 2 - Failure Latching

Select to latch input failure. If
a sensor fails an error is gen-
erated. This selection will
latch intermittent error.

Configuration Loop
Settings 2

Off (0)
On (1)

Off (0)

780 (R/W)

Analog Input 2 - Failure
Latching Acknowledge

Allow latched inputs errors to
be acknowleded and cleared if
sensor is repaired.

Monitor Device

No (0)
Yes (1)

Yes (1)

50 (R/W)

Loop 2 - Failure Fixed Power

Select output power level to
apply if sensor on input pro-
duces errors and transition to
manual (open loop) occurs.

Configuration Loop
Settings 2

-10000 to 10000 %
(two decimal places)

0

781 (R/W)
(/100)