Figure 40 — Process Output Configuration Web Page Tag Descriptions
Tag #
Process Output
Configuration Parameters
Parameter Description
Output
Selects the output function. Off (disabled), Control, Event or
Retransmit
Control Output Parameters
Selects the output direction. Off (disabled), Heat or Cool
Sets the minimum output power level available for the output. 0 to
100%.
Sets the maximum output power level available for the output. 0 to
100%.
Process Parameters
Selects the type of analog signal for the output. Voltage or Current.
Retransmit Parameters
11.
Source
Selects what variable is represented by the retransmit signal.
Process 1, Set Point 1, Process 2 or Set Point 2. Loop 2 parameters
available on dual channel model only.
12.
Scale Low
Sets the value represented by the low voltage or current scale. For
example, if you want a 1-5 Vdc signal to represent 30° to 100°C, set
Scale Low to 30.
13.
Scale High
Sets the value represented by the high voltage or current scale. For
example, if you want a 1-5 Vdc signal to represent 30° to 100°C, set
Scale High to 100.
Shifts the retransmit output signal up or down.
Event Output Parameters
Selects the logic function applied to the alarms and digital inputs
selected. AND or OR logic.
Selects the output state when the output is active. Energized or
De-engergized.