Process units, Low process scale, High process scale – Watlow Series PD User Manual
Page 67: Low voltage scale, High voltage scale, Low current scale, High current scale, Temperature process, Value units, Value precision

W a t l o w S e r i e s P D
■
65
■
C h a p t e r 9 D e v i c e C o n f i g T a b l e
Parameter Name
and Description
Web Page
Your
Settings
Range
Default
Modbus*
(Read/write and
scaling)
Analog Input 1 - Process UnitsSet the units for process type inputs that will be displayed in the browser only.,Configuration Analog Input
1,,,,1110-1111 (R)
Analog Input 1 - Low Process ScaleSet unit value for low process scale. This setting is the displayed process value when the analog input is
at minimum. ,Configuration Analog Input 1,,-30000000 to 30000000,-30000000,262-263 (R/W) (/1000)
Analog Input 1 - High Process ScaleSet unit value for high process scale. This setting is the displayed process value when the analog input
is at maximum. ,Configuration Analog Input 1,,-30000000 to 30000000,30000000,264-265 (R/W) (/1000)
Analog Input 1 - Low Voltage ScaleSet unit value for low end of voltage range. This setting determines range of input.,Configuration Ana-
log Input 1,,0 to 10000,0,258-259 (R/W) (/1000)
Analog Input 1 - High Voltage ScaleSet unit value for high end of voltage range. This setting determines range of input.,Configuration
Analog Input 1,,0 to 10000,10000,260-261 (R/W) (/1000)
Analog Input 1 - Low Current ScaleSet unit value for low end of current range. This setting determines range of input.,Configuration Ana-
log Input 1,,0 to 20000,4000,254-255 (R/W) (/1000)
Analog Input 1 - High Current ScaleSet unit value for high end of current range. This setting determines range of input.,Configuration
Analog Input 1,,0 to 20000,20000,256-257 (R/W) (/1000)
Analog Input 1 - Temperature Process Value UnitsSet the temperature units for thermocouple and RTD type inputs that will be displayed
in the browser only.,Configuration Analog Input 1,,(degrees symbol) F (0)(degrees symbol) C (1),(degrees symbol) F (0),1109 (R)
Analog Input 1 - Temperature Process Value PrecisionSet the decimal place for the input value of temperature when utilizing themocouple
or RTD input that will be displayed in the browser only.,Configuration Analog Input 1,,0 (0)0 (1),0 (0),1107 (R)
Analog Input 1 - Filter MethodSet the filter method. This smoothes out a rapidly changing input signal.,Configuration Analog Input 1,,Off
(0)First Order (1),Off (0),268 (R/W)
Analog Input 1 - Filter Time BaseSet the filter time for input in seconds.,Configuration Analog Input 1,,100 to 60000,100,269-270 (R/W)
(/1000)
Analog Input 1 - Single Offset ValueSet calibration single set point offset value. This allows compensation for lead resistance and sensor
error.,Configuration Analog Input 1,,-9999000 to 9999000,0,266-267 (R/W) (/1000)
Analog Input 1 - Failure Latching AcknowledgeAllows latched inputs errors to be acknowleded and cleared if sensor is repaired.,Monitor
DeviceTrend Information,,No (0)Yes (1),Yes (1),38 (R/W)
Analog Input 1 - Process Units
Set the units for process type
inputs that will be displayed
in the browser only.
Configuration Analog
Input 1
Up to four alpha-numeric
characters.
1110-1111 (R)
Analog Input 1 - Low Process
Scale
Set unit value for low process
scale. This setting is the dis-
played process value when the
analog input is at minimum.
Configuration Analog
Input 1
-30000000 to 30000000
units
-30000000
262-263 (R/W)
(/1000)
Analog Input 1 - High Process
Scale
Set unit value for high process
scale. This setting is the dis-
played process value when the
analog input is at maximum.
Configuration Analog
Input 1
-30000000 to 30000000
units
30000000
264-265 (R/W)
(/1000)
Analog Input 1 - Low Voltage
Scale
Set unit value for low end of
voltage range. This setting
determines range of input.
Configuration Analog
Input 1
0 to 10000 units
0
258-259 (R/W)
(/1000)
Analog Input 1 - High Voltage
Scale
Set unit value for high end of
voltage range. This setting
determines range of input.
Configuration Analog
Input 1
0 to 10000 units
10000
260-261 (R/W)
(/1000)
Analog Input 1 - Low Current
Scale
Set unit value for low end of
current range. This setting
determines range of input.
Configuration Analog
Input 1
0 to 20000 units
4000
254-255 (R/W)
(/1000)
Analog Input 1 - High Current
Scale
Set unit value for high end of
current range. This setting
determines range of input.
Configuration Analog
Input 1
0 to 20000 units
20000
256-257 (R/W)
(/1000)
Analog Input 1 - Temperature
Process Value Units
Set the temperature units for
thermocouple and RTD type
inputs that will be displayed
in the browser only.
Configuration Analog
Input 1
Fahrenheit (0)
Celsius (1)
Fahrenheit (0) 1109 (R)
Analog Input 1 - Temperature
Process Value Precision
Set the decimal place for the
input value of temperature
when utilizing themocouple or
RTD input that will be dis-
played in the browser only.
Configuration Analog
Input 1
0 (0)
0.0 (1)
0 (0)
1107 (R)