Watlow Series PD User Manual
Page 75
![background image](/manuals/359292/75/background.png)
W a t l o w S e r i e s P D
■
73
■
C h a p t e r 9 D e v i c e C o n f i g T a b l e
Parameter Name
and Description
Web Page
Your
Settings
Range
Default
Modbus*
(Read/write and
scaling)
Digital Input 4 - FunctionSet function for digital input.,Configuration Digital Input 4,,Off (0)Acknowledge Alarm (1)Switch To Manual
Control (2)Switch Control Loop Off (3)Digital Set point (4)Pause Data Logging (5),Off (0),371 (R/W)
Digital Input 4 - Active StateSet level when digital input is active.,Configuration Digital Input 4,,False (0)True (1),False (0),372 (R/W)
Digital Input 4 - StateDisplay state of digital input.,Configuration Digital Input 4,,Inactive (0)Active (1),Inactive (0),68 (R)
Digital Input 4 - Acknowledge Alarm ActionSpecify action when Digital Input 4 is used to acknowledge an alarm.,Configuration Digital In-
put 4,,Silence Alarm (0)Acknowledge Alarm (1)Silence and Acknowledge Alarm (2),Silence Alarm (0),388 (R/W)
Digital Input 4 - Select Ack Alarm 1Select to use Digital Input 4 to acknowledge Alarm 1.,Configuration Digital Input 4,,No (0)Yes (1),No
(0),373 (R/W)
Digital Input 4 - Select Ack Alarm 2Select to use Digital Input 4 to acknowledge Alarm 2.,Configuration Digital Input 4,,No (0)Yes (1),No
(0),374 (R/W)
Digital Input 4 - Select Ack Alarm 3Select to use Digital Input 4 to acknowledge Alarm 3.,Configuration Digital Input 4,,No (0)Yes (1),No
(0),375 (R/W)
Digital Input 4 - Select Ack Alarm 4Select to use Digital Input 4 to acknowledge Alarm 4.,Configuration Digital Input 4,,No (0)Yes (1),No
(0),376 (R/W)
Digital Input 4 - Select Ack Alarm 5Select to use Digital Input 4 to acknowledge Alarm 5.,Configuration Digital Input 4,,No (0)Yes (1),No
(0),377 (R/W)
Digital Input 4 - Select Ack Alarm 6Select to use Digital Input 4 to acknowledge Alarm 6.,Configuration Digital Input 4,,No (0)Yes (1),No
(0),378 (R/W)
Digital Input 4 - Function
Set function for Digital Input 4.
Configuration Digital
Input 4
Off (0)
Acknowledge Alarm (1)
Switch To Manual Control (2)
Switch Control Loop Off (3)
Digital Set Point (4)
Pause Data Logging (5)
Off (0)
371 (R/W)
Digital Input 4 - Active State
Set level when Digital Input 4
is active.
Configuration Digital
Input 4
False (0)
True (1)
False (0)
372 (R/W)
Digital Input 4 - State
Display state of Digital Input 4.
Configuration Digital
Input 4
Inactive (0)
Active (1)
Inactive (0)
68 (R)
Digital Input 4 - Acknowledge
Alarm Action
Specify action when Digital
Input 4 is used to acknowl-
edge an alarm.
Configuration Digital
Input 4
Silence Alarm (0)
Acknowledge Alarm (1)
Silence and Acknowledge
Alarm (2)
Silence Alarm
(0)
388 (R/W)
Digital Input 4 - Select
Acknowledge Alarm 1
Select to use Digital Input 4
to acknowledge Alarm 1.
Configuration Digital
Input 4
No (0)
Yes (1)
No (0)
373 (R/W)
Digital Input 4 - Select
Acknowledge Alarm 2
Select to use Digital Input 4
to acknowledge Alarm 2.
Configuration Digital
Input 4
No (0)
Yes (1)
No (0)
374 (R/W)
Digital Input 4 - Select
Acknowledge Alarm 3
Select to use Digital Input 4
to acknowledge Alarm 3.
Configuration Digital
Input 4
No (0)
Yes (1)
No (0)
375 (R/W)
Digital Input 4 - Select
Acknowledge Alarm 4
Select to use Digital Input 4 to
acknowledge Alarm 4.
Configuration Digital
Input 4
No (0)
Yes (1)
No (0)
376 (R/W)
Digital Input 4 - Select
Acknowledge Alarm 5
Select to use Digital Input 4
to acknowledge Alarm 5.
Configuration Digital
Input 4
No (0)
Yes (1)
No (0)
377 (R/W)
Digital Input 4 - Select
Acknowledge Alarm 6
Select to use Digital Input 4
to acknowledge Alarm 6.
Configuration Digital
Input 4
No (0)
Yes (1)
No (0)
378 (R/W)