Watlow Series PD User Manual
Page 76
W a t l o w S e r i e s P D
■
74
■
C h a p t e r 9 D e v i c e C o n f i g T a b l e
Parameter Name
and Description
Web Page
Your
Settings
Range
Default
Modbus
(Read/write and
scaling)
Digital Input 4 - Select Ack Alarm 7Select to use Digital Input 4 to acknowledge Alarm 7.,Configuration Digital Input 4,,No (0)Yes (1),No
(0),379 (R/W)
Digital Input 4 - Select Ack Alarm 8Select to use Digital Input 4 to acknowledge Alarm 8.,Configuration Digital Input 4,,No (0)Yes (1),No
(0),380 (R/W)
Digital Input 4 - Switch To Manual Loop 1,Configuration Digital Input 4,,No (0)Yes (1),No (0),381 (R/W)
Digital Input 4 - Switch To Manual Loop 2,Configuration Digital Input 4,,No (0)Yes (1),No (0),382 (R/W)
Digital Input 4 - Switch Control Loop 1 Off,Configuration CT Input 4,,No (0)Yes (1),No (0),383 (R/W)
Digital Input 4 - Switch Control Loop 2 Off,Configuration Digital Input 4,,No (0)Yes (1),No (0),384 (R/W)
Digital Input 4 - Digital Set pointSpecify Digital Set Point value to switch to when Digital Input 4 is activated.,Configuration Digital Input
4,,,75000,386-387 (R/W) (/1000)
Digital Input Switch Control Loop Off Status,Monitor Device,,Inactive (0)Active (1),Inactive (0),63 (R)
Digital Input Switch Control Loop Off Status,Monitor Device,,Inactive (0)Active (1),Inactive (0),70 (R)
Digital Input Switch to Manual Control Status,Monitor Device,,Inactive (0)Active (1),Inactive (0),62 (R)
Digital Input Switch To Manual Control Status,Monitor Device,,Inactive (0)Active (1),Inactive (0),69 (R)
Digital Input 4 - Select
Acknowledge Alarm 7
Select to use Digital Input 4
to acknowledge Alarm 7.
Configuration Digital
Input 4
No (0)
Yes (1)
No (0)
379 (R/W)
Digital Input 4 - Select
Acknowledge Alarm 8
Select to use Digital Input 4
to acknowledge Alarm 8.
Configuration Digital
Input 4
No (0)
Yes (1)
No (0)
380 (R/W)
Digital Input 4 - Switch To
Manual Loop 1
Select to use Digital Input 4
to switch Loop 1 to manual
mode of control.
Configuration Digital
Input 4
No (0)
Yes (1)
No (0)
381 (R/W)
Digital Input 4 - Switch To
Manual Loop 2
Select to use Digital Input 4
to switch Loop 2 to manual
mode of control.
Configuration Digital
Input 4
No (0)
Yes (1)
No (0)
382 (R/W)
Digital Input 4 - Switch Con-
trol Loop 1 Off
Select to use Digital Input 4
to switch control Loop 1 off.
Configuration CT In-
put 4
No (0)
Yes (1)
No (0)
383 (R/W)
Digital Input 4 - Switch Con-
trol Loop 2 Off
Select to use Digital Input 4
to switch control Loop 2 off.
Configuration Digital
Input 4
No (0)
Yes (1)
No (0)
384 (R/W)
Digital Input 4 - Digital Set
Point
Specify Digital Set Point
value to switch to when
Digital Input 4 is activated.
Configuration Digital
Input 4
Within set point limits
75000
386-387 (R/W)
(/1000)
Digital Input Switch Control
Loop 1 Off Status
Indicates that a digital input
is forcing Control Loop 1 off.
Monitor Device
Inactive (0)
Active (1)
Inactive (0)
63 (R)
Digital Input Switch Control
Loop 2 Off Status
Indicates that a digital input
is forcing Control Loop 2 off.
Monitor Device
Inactive (0)
Active (1)
Inactive (0)
70 (R)
Digital Input Switch Control
Loop 1 to Manual Control
Status
Indicates that a digital input
is forcing Control Loop 1 to
manual mode of operation.
Monitor Device
Inactive (0)
Active (1)
Inactive (0)
62 (R)
Digital Input Switch Control
Loop 2 To Manual Control
Status
Indicates that a digital input
is forcing Control Loop 2 to
manual mode of operation.
Monitor Device
Inactive (0)
Active (1)
Inactive (0)
69 (R)