beautypg.com

Removing a bcm400 redundant power supply cage, To remove a bcm400 redundant power supply cage, Figure 155 – Nortel Networks BCM200/400 User Manual

Page 301

background image

Chapter 23 Replacing or upgrading a power supply

301

BCM200/400 4.0 Installation and Maintenance Guide

Figure 155 Install a cable grommet

20 Install the main unit top cover. See

“Installing the main unit top cover” on page 254

.

Removing a BCM400 redundant power supply cage

Use this procedure to remove an existing redundant power supply cage from the BCM400 main
unit.

To remove a BCM400 redundant power supply cage

1

Set up the BCM400 for maintenance (see

“Performing a system shutdown” on page 239

).

2

Disconnect all cables from the front of the base function tray.

3

Disconnect the main unit and the expansion unit (if applicable), from the AC power
connection.

4

Remove the top cover from the BCM400 main unit (see

“Removing the main unit top cover”

on page 252

).

5

Attach one end of the grounding strap to your wrist and the other end to a grounded metal
surface.

6

Remove the power supply modules (see

“Removing a power supply module” on page 305

).

7

Partially remove the power supply module from the power supply cage. Do not completely
remove the power supply module.

Warning: Protect the hardware components against damage from electrostatic discharge.
Always wear a grounded wrist strap before you handle components. Always place the
components in a static-free container.

Cable grommet

Insert the P2, P3
and auxiliary
cables into the
cable slot

Cable slot