6.2 Troubleshooting
393
D
Display and Outputs
Digital Operator
Di l
d
Alarm Output
g
p
Display and
Alarm Name
Alarm Code Output
Alarm Output
Alarm Name
ALO1
ALO2
ALO3
p
A.04
User constant
setting error
OFF
OFF
OFF
OFF
OFF: Output transistor is OFF
ON: Output transistor is ON
Status When Alarm Occurred
At control power ON
A
,
B
Cause
Remedy
A
An out-of-range user constant was
previously set or loaded.
Reset all user constants in range.
Otherwise, re-load correct user constants.
B
Circuit board (1PWB) defective
Replace Servopack.
D
Display and Outputs
Digital Operator
Di l
d
Alarm Output
g
p
Display and
Alarm Name
Alarm Code Output
Alarm Output
Alarm Name
ALO1
ALO2
ALO3
p
A.10
Overcurrent
ON
OFF
OFF
OFF
OFF: Output transistor is OFF
ON: Output transistor is ON
Note
Alarm A10 is reset when the power is turned OFF and back ON. It is not reset by the normal
alarm reset.
Status When Alarm Occurred
During servomotor
operation
When servo ON (S-ON)
signal turned ON
A
,
B
,
C
, D, E
D,
E
At main circuit power
ON
D
6